20
Converter mode
The UPS is operating
on converter mode.
In converter mode, the UPS would free run
with fixed output frequency (50Hz or
60Hz). Once the mains is loss or abnormal,
the UPS would transfer to battery mode
and the load is supplied continuously.
1. The function could be enabled through
the LCD setting or the software
(Winpower, etc.).
2. The load should be derating to 60% in
converter mode.
Warning
There are some
abnormal problems
during the operation of
UPS. Normally the
problems are not fatal
The UPS continues working, but please pay
attention to the warning, or the UPS may
fail.
Fault
Some fatal problems
happened
The UPS will cut off the output or transfer
to bypass mode at once, and keep
alarming.
Overload
The load exceeds the
capacity of the UPS
Some unnecessary loads should be cut off
one by one to reduce the load connected
to the UPS.
Battery test
UPS is executing a
battery test
Test the battery
Battery fail
The UPS detects bad
battery or battery
disconnected
The symbol of battery failure would be
shown and UPS would alarm.
UPS Parallel
Using two or three UPS
for heavy load or
redundancy
Two or three UPS operation in parallel