Tandem ELF current-limiting dropout fuse installation instructions

INSTALLATION INSTRUCTIONS

   MN132029EN   November 2016

!

 WARNING 

Do not attempt to interrupt load current by pulling on 

the Tandem ELF fuse pull ring to open the cutout . An arc 

started by opening a cutout under load in this manner 

could cause injury or damage to equipment .

otee:

N

Interchangeable cutouts are equipped with hooks 

for use with a loadbreak tool. To open the Tandem 

ELF fuse from the cutout, use ONLY an approved 

loadbreak tool designed for use with cutouts and 

follow the instructions provided with such tool.

Operation and refusing

!

 CAUTION 

Only qualified personnel should operate a cutout . Such 

personnel should always wear appropriate protective 

equipment such as rubber gloves, hard hats, safety 

glasses, etc ., in accordance with established utility and 

safety practices .

!

 CAUTION 

A Tandem ELF fuse open in a cutout  indicates a blown 

fuse due to an overload or fault condition . Faults and/or 

visibly failed equipment should be located and repaired 

before refusing a Tandem ELF fuse .

When the Tandem ELF fuse (refer to Figure 6) operates, the 

fuse will drop open in the cutout.

Removal of the tandem ELF fuse

1. 

Insert a hook stick into the lifting eye of the Tandem 

ELF fuse and remove it from the hinge of the cutout . 

!

 CAUTION 

If the Tandem ELF fuse operates for a high current fault, 

the backup current-limiting fuse may be hot enough to 

cause burns . Wear gloves and handle the Tandem ELF 

fuse by the fuse link holder to avoid burns .

Testing of the backup current-limiting fuse

The backup current-limiting fuse should always be tested 

after an operation of the Tandem ELF fuse. 

1. 

Perform a continuity check on the backup  

current-limiting fuse as shown in Figure 7 . 

!

 CAUTION 

Failure to check the Tandem ELF’s backup current-

limiting fuse may result in placing an operated/

damaged fuse back in service .  This could result in 

personal injury, fire, or equipment damage .

2. 

If the backup current-limiting fuse does not have 

continuity,

 change out the fuses as described in 

“Refusing the Backup Current-Limiting Fuse” on 

page 6. 

If the fuse does have continuity,

 skip to 

“Refusing Fuse Link in Fuse Link Holder” on page 6. 

Tandem elf 

fuse

(Operated)

Lifting eye

Pull ring

Insulator

Lower

Connector

Hinge

Figure 6 .  Tandem ELF fuse in Type L cutout after 

operation

Содержание Tandem ELF Current-Limiting Dropout Fuse

Страница 1: ...stallation Instructions Upper contact Upper pull ring connector Pull ring Backup current limiting fuse Fuse link holder Lifting eye Fuse cap COOPER POWER SERIES Fusing Equipment MN132029EN Effective N...

Страница 2: ...PURPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHAL...

Страница 3: ...TION 1 Introduction 1 Acceptance and initial inspection 1 Handling and storage 2 Standards 2 APPLICATION 2 INSTALLING A FUSE LINK IN FUSE LINK HOLDER 3 INSTALLING A TANDEM ELF FUSE IN CUTOUT 3 OPERATI...

Страница 4: ...nt Additional statements related to specific tasks and procedures are located throughout the manual Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or sever...

Страница 5: ...rly coordinated fuse links the fuse link will operate to provide for the dropout action of the Tandem ELF fuse following an interruption Read this manual first Read and understand the contents of this...

Страница 6: ...es catalog section CA132028EN or contact your Eaton representative Installation procedure The Tandem ELF fuse is shipped only with the backup current limiting fuse installed Remove the fuse link if su...

Страница 7: ...a tandem ELF fuse in cutout Once the fuse link has been installed in the fuse link holder 1 Insert the hook stick into the Tandem ELF fuse s lifting eye 2 Place the Tandem ELF fuse into the hinge of...

Страница 8: ...When the Tandem ELF fuse refer to Figure 6 operates the fuse will drop open in the cutout Removal of the tandem ELF fuse 1 Insert a hook stick into the lifting eye of the Tandem ELF fuse and remove i...

Страница 9: ...in Installing a Fuse Link in Fuse Link Holder on page 2 Maintenance Refer to ANSI Standards C37 48 as a general guide for maintenance of the cutout 1 Periodically inspect the fuse link at the lower en...

Страница 10: ...6 Tandem ELF current limiting dropout fuse installation instructions INSTALLATION INSTRUCTIONS MN132029EN November 2016 This page is intentionally left blank...

Страница 11: ...7 Tandem ELF current limiting dropout fuse installation instructions INSTALLATION INSTRUCTIONS MN132029EN November 2016 This page is intentionally left blank...

Страница 12: ...States Eaton com cooperpowerseries 2016 Eaton All Rights Reserved Printed in USA Publication No MN132029EN Rev 0 November 2016 Eaton is a registered trademark All trademarks are property of their res...

Отзывы: