SVS/12
94
994.530 G01 02
O
PTION
As an option, it is possible to have an arrangement
whereby the protection cover can only be removed if the
cable is earthed and the interlock strip is pulled out.
In this case, the load-break switch can no longer be locked
to prevent switching off in the operating position.
Procedure:
Fundamental principle:
The cable is earthed (disconnector in earthing position,
switch closed).
To open the door:
Pull the interlock strip (9) out and open the door with
the key.
To close the door:
Pull the interlock strip (9) out and close the door with
the key.