CLEARING FAILURE CODES:

• 

A battery failure (LED two blink red) can be cleared by 
replacing the battery. Disconnecting the battery and AC 
power, or performing a full 90 minute discharge, will 
reset the error code, however, it will return if the battery 
is faulty.

• 

Charge Circuit (LED three blink red) and lamp/LED 
failure (LED four blink red) will clear when the unit suc-
cessfully passes a manual or automatic 30 second test.

INDICATORS:

 

• 

LED Off - No power to unit, emergency mode.

• 

LED Steady Green - Unit is fully charged and is fl oat 
charging the battery to maintain readiness.

• 

LED Green Pulse - Unit is in a 24 hour fast charge of 
the battery.

• 

LED Two Blink Red - Battery has failed a capacity test, 
or the battery is disconnected. See “Clearing Failure 
Codes” above.

• 

LED Three Blink Red - Battery charge circuit has failed. 
See “Clearing Failure Codes” above.

• 

LED Four Blink Red - Lamps have burned out, or on 
an EXIT/Combo, 50% or more of the LEDs have failed. 
See “Clearing Failure Codes” above.

• 

LED Steady Yellow - 30 second test or 10 second quick 
test (Fast Charge only).

• 

LED Blinking Yellow - 90 minute test

MAINTENANCE:

 

None required. Replace the batteries as needed according 
to ambient conditions. Equipment should be tested every 
30 days in accordance with local codes.

NOTE:

 Servicing of any parts should be performed by quali-

fi ed personnel. Only use replacement parts supplied by Ea-
ton Light. Use of unauthorized parts may void the warranty.

CAUTION:

 This equipment is furnished with a sophisticated 

low voltage battery dropout circuit to protect the battery 
from over discharge after its useful output has been used. 
Allow 24 hours recharge time after installation or power 
failure prior to 90 minute testing.

TROUBLE SHOOTING GUIDE

If LED heads or charge indicator LED does not illuminate, 
check the following:
1.  Check AC supply – verify that unit has 24 hour AC 

supply.

2.  Unit is shorted or battery is not connected.
3.  Battery discharged. Permit unit to charge for 24 hours 

and then re-test.

4.  If following the above trouble shooting hints does not 

solve your problem, contact your local Eaton Light rep-
resentative for assistance

JMP12

JMP11

JMP10

JMP9

JMP8

JMP7

JMP6

JMP5

JMP4

BATT

LAMPS

N

c

TDI

ICSP

277

JMP13

JMP14

LED/SW

D5

C6

C7

C8

C9

CN4

F1

J1

JK

1

LED1

MOV1

MOV2

PR1

Q1

Q5

R7

R10

R1

3

R15

R18

R30

SW1

120

CN5

+

+

WHITE LEAD - TO NEUTRAL

BLACK LEAD - TO 120V

ORANGE LEAD - TO 277V 

CHARGER/DRIVER PCB

BATTERY

LED HEADS

OFF - EMERGENCY
MODE / POWEROFF

2 BLINK RED -
BATTERY FAILURE

STEADY GREEN -
FULL / FLOAT
CHARGE

STEADY BLINK YELLOW
- 90 MINUTE TEST

3 BLINK RED - CHARGE

 

CIRCUIT FAILURE

4 BLINK RED - LAMP/
LED FAILURE

STEADY YELLOW -
QUICK TEST

STEADY BLINK
GREEN - FAST

 

CHARGE

SURE-LITES

 

TIME DELAY 
JUMPER