background image

ACTIVATING TIME DELAY

The SELW29SD has an integrated time delay circuit that 
allows them to remain in emergency mode 15 minutes after 
power is restored.
To activate the time delay, remove the jumper on the circuit 
board labe

led

 TDI/J1.

OPERATION

The Sure-Lites Eagle Eye Self Diagnostics is continuous-
ly monitoring your emergency 

 xture, and will signal any 

failure through the 3 color indicator LED.

INITIAL OPERATION

When the unit is 

 rst powered up, it will go into a 24 hour 

fast charge, indicated by the indicator LED pulsing green. 
Once the unit has fully charged, it will perform a self cali-
bration, after which the LED will change to steady green, 
indicating the unit is fully charged and 

 oat charging the 

battery to maintain readiness.

AUTOMATIC TESTING

The unit will perform a battery capacity, lamp/LED, and 
charge circuit test every 30 days for 30 seconds. During 
this time, the indicator LED will change to a steady yellow. 
It will perform a full battery capacity (90 minute) test once 
per year. During this time, the indicator LED will change to 
a blinking yellow.

MANUAL TESTING 

• 

10 Second “Installation” test – Press and release the 
test button once during fast charge (blinking green) to 
initiate a 10 second quick test. The sign will switch to 
emergency mode for 10 seconds allowing the installer 
to verify proper installation of the unit, and the LED 
indicator will turn solid yellow.

• 

30 Second Test - Press and release the test button 
once during 

 oat charge (steady green). The indica-

tor LED will turn steady yellow to indicate the unit is 
performing a 30 second test of the batteries and lamps/
LEDs.

• 

90 Minute Test - Press and release the test button a 
second time during a 30 second test (steady yellow) to 
change to a 90 minute test. During this test, the LED 
indicator will change to blinking yellow, and the circuit 
will perform a full battery capacity, charge circuit, and 
LED test.

• 

Canceling Test – Press and release the test button 
during the 90 minute test (

 ashing yellow) to return the 

 xture to its original state (fast charge or 

 oat charge).

LASER TEST:

The SELW29SD is equipped with a Laser Test function, 
that allows the unit to be manually tested without the need 
to physically press the test button. Shining a laser pointer 
in the hole marked “LASER TEST” on the bottom of the 
unit has the same effect as a press and release of the test 
button.

Figure 2

Figure 1

FOR BEST 
RESULTS MOUNT 
WITH ARROW 
FACING UP