ACTIVATING TIME DELAY
The SELW29SD has an integrated time delay circuit that
allows them to remain in emergency mode 15 minutes after
power is restored.
To activate the time delay, remove the jumper on the circuit
board labe
led
TDI/J1.
OPERATION
The Sure-Lites Eagle Eye Self Diagnostics is continuous-
ly monitoring your emergency
fi
xture, and will signal any
failure through the 3 color indicator LED.
INITIAL OPERATION
When the unit is
fi
rst powered up, it will go into a 24 hour
fast charge, indicated by the indicator LED pulsing green.
Once the unit has fully charged, it will perform a self cali-
bration, after which the LED will change to steady green,
indicating the unit is fully charged and
fl
oat charging the
battery to maintain readiness.
AUTOMATIC TESTING
The unit will perform a battery capacity, lamp/LED, and
charge circuit test every 30 days for 30 seconds. During
this time, the indicator LED will change to a steady yellow.
It will perform a full battery capacity (90 minute) test once
per year. During this time, the indicator LED will change to
a blinking yellow.
MANUAL TESTING
•
10 Second “Installation” test – Press and release the
test button once during fast charge (blinking green) to
initiate a 10 second quick test. The sign will switch to
emergency mode for 10 seconds allowing the installer
to verify proper installation of the unit, and the LED
indicator will turn solid yellow.
•
30 Second Test - Press and release the test button
once during
fl
oat charge (steady green). The indica-
tor LED will turn steady yellow to indicate the unit is
performing a 30 second test of the batteries and lamps/
LEDs.
•
90 Minute Test - Press and release the test button a
second time during a 30 second test (steady yellow) to
change to a 90 minute test. During this test, the LED
indicator will change to blinking yellow, and the circuit
will perform a full battery capacity, charge circuit, and
LED test.
•
Canceling Test – Press and release the test button
during the 90 minute test (
fl
ashing yellow) to return the
fi
xture to its original state (fast charge or
fl
oat charge).
LASER TEST:
The SELW29SD is equipped with a Laser Test function,
that allows the unit to be manually tested without the need
to physically press the test button. Shining a laser pointer
in the hole marked “LASER TEST” on the bottom of the
unit has the same effect as a press and release of the test
button.
Figure 2
Figure 1
FOR BEST
RESULTS MOUNT
WITH ARROW
FACING UP
SEL-SD Emergency Lights Installation Instructions
www.
eaton.com/lighting
2