Tripp Lite by Eaton SmartOnline Series User Guide 614-21326—Rev 01
17
Table 7. User Settings (Continued)
Main Menu Screen
Submenu
Submenu
Menu Function
OUTPUT FREQUENCY
AUTOSENSING* (Default)
[AUTO SENSING] [FREQ
CONV. 50HZ] [FREQ CONV.
60HZ]
Sets the output frequency,
output frequency follows the
input frequency,
HIGH EFFIC. MODE
DISABLED* (Default)
[ENABLED] [DISABLED]
Power the output from bypass
for high efficiency
OVERLOAD PREALARM
102%* (Default) [50%]
[55%]....[100%][102%]
Load % when overload alarm
occurs
ON / OFF SETTINGS
COLD START
ENABLED* (Default)
[ENABLED] [DISABLED]
Allows the SmartOnline UPS
to start on battery power.
AUTO RESTART
ENABLED* (Default)
[ENABLED] [DISABLED]
Allows the SmartOnline UPS
to restart automatically when
mains recovers after a
complete battery discharge.
AUTO START
ENABLED* (Default)
[ENABLED] [DISABLED]
The SmartOnline UPS starts
up as soon as mains power is
available.
START ON BYPASS
ENABLED* (Default)
[ENABLED] [DISABLED]
Allows the SmartOnline UPS
to start in bypass mode.
SLEEP MODE
ENABLED* (Default)
[ENABLED] [DISABLED]
If Disabled, LCD and
communication will turn off
immediately afterSmartOnline
UPS is OFF. If Enabled, LCD
and communication stays ON
1h30 min after the
SmartOnline UPS is OFF.
SITE WIRING FLT
ENABLED* (Default)
[ENABLED] [DISABLED]
Prevents the SmartOnline UPS
from starting in case of phase
to neutral wire swapping or
improper grounding,
BATTERY SETTINGS
AUTO BAT TEST
MONTHLY*(Default) [NO
TEST] [DAILY] [WEEKLY]
[MONTHLY]
Allows the SmartOnline UPS
to perform an automatic
battery test.
RESTART LEVEL
0%* (Default) [0%]....[100%]
Allows the SmartOnline UPS
to restart when the set
percentage battery charge is
reached.
BATT LOW LEVEL
0%* (Default) [0%]....[100%]
The alarm triggers when the
set percentage of battery
charge is reached.
BATT LOW TIME
3 MIN* (Default) [0MIN]
[3MIN] .. [60MIN]
The alarm triggers when the
set battery time remaining is
reached.
Содержание SU700XLCD
Страница 12: ...6 Tripp Lite by Eaton SmartOnline Series User Guide 614 21326 Rev 01 Rear Panels...
Страница 30: ...24 Tripp Lite by Eaton SmartOnline Series User Guide 614 21326 Rev 01 Cybersecurity...
Страница 34: ...28 Tripp Lite by Eaton SmartOnline Series User Guide 614 21326 Rev 01 Retrieving the Event Log...
Страница 40: ...34 Tripp Lite by Eaton SmartOnline Series User Guide 614 21326 Rev 01 Recycling the used equipment...
Страница 46: ...40 Tripp Lite by Eaton SmartOnline Series User Guide 614 21326 Rev 01 Service and Support...
Страница 51: ...Tripp Lite by Eaton SmartOnline Series User Guide 614 21326 Rev 01 45 Model Specifications...
Страница 52: ...614 2132601 614 21326 01...