Eaton Static Transfer Switch 2000A 3-Pole Installation and Operation Manual 164001127—Rev 01
25
C
Chhaapptteerr 55 IInnssttaallllaattiioonn aanndd S
Sttaarrttuupp P
Prroocceedduurreess
•
Severe or fatal injury can result from electrical shock during contact with high voltage conductors,
monitoring PCBs, or similar equipment.
•
Disconnect power before drilling holes, attaching cables or conduit, or connecting PDUs to other power
distribution equipment.
•
Use Lock Out/Tag Out procedures.
•
Wear suitable personal protective clothing and use protective equipment for performing mechanical and
electrical installations.
•
Leave ample space for attaching and routing wires.
!
IMPORTANT
•
A licensed electrician must install each unit.
•
Startup by an Eaton certified technician is required to validate the warranty.
•
To validate the warranty, please complete the Warranty Validation Request form and notify Eaton PDI
Service Department upon completion of the startup to initiate the Warranty Coverage.
Installation is the responsibility of the Installer, who may be an Installing Contractor. The Installer must be an
electrician certified for the locality where the installation is being performed.
An Eaton-certified technician must perform or witness Commissioning and Start-up of the STS 2000A unit to
validate the warranty.
55..11
IInnssttaallllaattiioonn IInnssttrruuccttiioonnss
55..11..11
P
Poossiittiioonniinngg tthhee S
STTS
S 22000000A
A U
Unniitt
The stand-alone STS 2000A requires front access for normal operation and both front and rear access for
installation and maintenance.
1.
1. The standalone STS 2000A requires 30" front and rear access for installation and maintenance, allowing
the unit to be fully serviced and complying with the 1996 National Electric Code for access to Circuit
Breaker distribution equipment.
2.
Check STS floor loading to verify that the STS 2000A system does not exceed the raised floor loading
specifications. System weight and cabinet dimensions are given in
.
3.
If additional raised floor supports are required, contact Eaton Service (1-800-843-9433) or your raised floor
manufacturer for either floor jacks or full frame floor stands and their specifications.
4.
The STS 2000A does not have casters or leveling feet because of the weight of the unit.
55..11..22
M
Maakkee P
Poow
weerr C
Coonnnneeccttiioonnss
After the STS 2000A unit is correctly positioned, make power connections to input and output buses as
described in
Содержание STS 2000A
Страница 1: ...p n 164001127 Revision 01 Installation and Operation Manual Eaton Static Transfer Switch 2000A 3 Pole...
Страница 8: ......
Страница 16: ...xvi Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 List of Tables...
Страница 32: ...16 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Safety...
Страница 98: ...82 Eaton Static Transfer Switch 2000A 3 Pole Installation and Operation Manual 164001127 Rev 01 Troubleshooting...
Страница 120: ...16400112701 164001127 01...