Technical Specification –SPDV60-300 

Tvss Doc# 510083 

Page 1 of 2 

 

Web: 

http://www.powerware.com.au

 Phone: 1300 UPS UPS

 

SPDV60-300 

S

URGE 

D

IVERTER

 

(Single mode, 220-250V (380-440V), 60/30kA) 

INSTALLATION INSTRUCTIONS 

FEATURES 

• 

1 mode plug-in protection (L-N) 

• 

Compact solution for primary protection 

• 

DIN43880 base, 35 mm DIN-rail mountable 

• 

MOV is thermally protected 

• 

Includes dry-contact alarm

 

Applications 

• 

Mains point-of-entry /Main SWB 

• 

Telecommunication Systems / Rectifiers 

• 

Process and Control Systems / Factories & Units 

• 

Computer Systems / Medical Systems 

• 

All sensitive Electronic Equipment

 

FUNCTIONAL DESCRIPTION  

The SPDV60-300 is designed to protect single and 3-
phase power systems against damage from surges 
and spikes caused by lightning and other electrical 
sources. The unit is intended for point-of-entry or 
sub-board protection and is connected in parallel with 
the power system via HRC fuses. The unit features a 
plug-in module that may be replaced without rewiring 
in the event of a fault. Check that the model you have 
purchased is rated correctly for your power system. 

This model (SPDV60-300) is designed for single 
and 3-phase power systems, with a grounded 
neutral, in the range of 220-250V(380-440V). If 
your power system is “delta” (i.e. ungrounded), 
or a different voltage, this model is NOT suitable

.  

 
Please contact your supplier for a suitable model to 
suit your application. 

 
OPERATION 

The operational status of the unit is shown by a flag 
indicator on the front of the module. In normal 
operation, the flag is green. If the unit becaomes 
damaged, the flag changes to red, indicating that 
replacement is necessary. A ‘dry-contact’ alarm 
output is fitted to the base unit and will change over if 
the module is faulty or not in place.

 

 

WARRANTY

  

Eaton Power Quality warrants this unit against faulty 
parts and workmanship for a period of 12 months 
from the date of purchase. If this product fails to 
operate correctly, please contact your Eaton 
representative. This warranty doesn’t cover neglect 
or intentional misuse. As this product is intended for 
use in electrically harsh environments no claim is 
made of suitability for purpose. This unit is designed 
to reduce the likelihood of damage, not prevent it. 
Please also note that an excessive surge, such as 
from a direct lightning strike to the site or a power 
system fault, may cause damage to the unit and 
render it inoperable. A unit that has been damaged in 
this way is not warrantable. 

 

 

 
 

For installation details,  

see over page. 

SPECIFICATIONS

 

Manufacturers name and model 

Eaton Powerware 
SPDV60-300 

Method of mounting 

Fixed. DIN Rail mount 

Input voltage 

220-250VAC (380-440V) 
40-70Hz 

Maximum continuous operating 
voltage - MCOV 

300VAC 

Service type 

TN-C and TN C-S (3-phase 
with grounded neutral) 

Test classification  

Class II 

Supply current 

<10mA 

Initial clamp voltage 

470V 

Maximum rated surge current - 
Ismax 8/20us  

60kA 

Nominal surge current - In 
8/20us 

30kA 

Residual voltage (Vpl) @  
3kA, 8/20uS 

1.0kV 

Residual voltage (Vpl) @ Ismax 
30kA, 8/20uS 

1.4kV 

Energy absorbtion (2ms) 

2130j 

Nominal surge lifetime (In) 

30kA (8/20uS), 20 times 

Internal protection 

MOV thermal disconnect 
device 

External disconnector 
requirements 

Gg/Gl HRC fuses, 1 per 
unit/phase, 160A maximum.

 

Terminations 

Power terminals 25mm

2

 , 

Alarm terminals 1.5mm

2

 

Alarms/indicators 

Flag indicator, dry contact 
alarm relay  – 
250VAC/24VDC, 2A 

Location Category 

Indoor 

Enclosure rating 

IP20 

Applicable standards. 

IEC61643-1, IEC610006, 
ANSI/IEEE C62.41, 
AS1768-1991, AS3100  

Dimensions 

DIN43880, 1 units (17mm) 

Weight 

100g 

Environment 

-10 to 60C, 0-90%RH 

Warranty 

12 months, workmanship 
and materials 