Eaton SPDV60-300 Скачать руководство пользователя страница 2

 

 

Specification are subject to change without notice. Copyright 2007 Eaton Power Quality Pty Ltd 

Technical Specification –SPDV60-300 

Tvss Doc# 510083 

Page 2 of 2 

 

Web: 

http://www.powerware.com.au

 Phone: 1300 UPS UPS

 

INSTALLATION 

Refer to the procedure and diagram shown to connect the 
SPDV60-300. 

PROCEDURE:

 

1. CHECK 

• 

Always work safely – disconnect power before 
making connections. 

• 

All wiring must be carried out by suitably qualified 
personnel according to the applicable standards. 

• 

Check for correct operating voltage and power 
system. This model (SPDV60-300) is designed for 
power systems in the range of 220-250V(380-
440V). 

If your power system is “delta” (i.e. 

ungrounded), or a different voltage, this model 
is not suitable

. Please contact your supplier. 

• 

** For installation adjacent to an M.E.N. link, use  
as shown. 

• 

** For installations remote from the M.E.N., a 
separate N-E protector is required (SPD50Ngi). 

• 

Always use the correct size HRC fuses.  

• 

For services >160A, use 160A fuses. For services 
<160A, no fuse is necessary however an SPD 
fault may cause a loss of power to the site. 

 

• 

Always use Gg or Gl-rated fuses. Do not use 
delay types or ‘semiconductor’ fuses. 

• 

For 80A domestic supplies, no fuse is necessary. 

2. INSTALL 

• 

Locate a fuse position as close as possible to the 
Main Switch. 

• 

Install fuseholders or fuse-switch. 

• 

Locate a suitable position for the SPD, ensuring 
adequate space for cables. Do not install above 
heat-generating objects or in any position that is 
exposed to weather. 

• 

Install unit to DIN-rail in switchboard or cabinet. 

3. CONNECT 

• 

Connect wiring - refer to connection diagrams. If 
using stranded cable, always use wire ferrules for 
lowest resistance and to prevent damage to the 
wire. 

• 

Use a suitably-rated cable for power connections. 
Cable should be rated for operation at the system 
voltage and should be 6mm

2

 to 25mm

2

• 

Use short cables for all connections or protection 
will be reduced.

 

• 

Use a suitably-rated cable for alarm connections. 
Cable should be rated for operation at the system 
voltage and should be 0.5mm

2

 to 1.5mm

2

 

4. NOTES: 

• 

160A fuses are rated such for maximum surge 
rating. On services below 160A, high-level surges 
may cause disconnection of the supply.

 

• 

Wiring from fuse to SPD is carrying surge currents 
only, not load current. This means that smaller 
cables may be used than is normal for the current 
rating. 

 

• 

If using under-sized cables, some energy 
authorities require double insulation (i.e. sleeving) 
of the cables.

 

• 

Maximum alarm relay resistive load is 2A.

 

• 

Unplug the alarm connector for termination.

 

• 

It is recommended not to connect the alarm 
contacts to AC mains circuits if possible, to 
prevent flashover from surges on the AC line. 
Connect to a PLC or BMS if available.

 

• 

Do not Megger test cabling with unit connected – 
unit may be damaged.

 

 

EARTHING 

For proper operation, all surge diverters rely upon a good 
earth connection: 

• 

The main earth wire (from earth link on switchboard to 
ground rod or system) MUST be as short and direct as 
possible.  Extra cable must not be looped. 

• 

Earth connections from the unit to neutral or earth link 

MUST

 be as short as possible. 

 

 
Failure to consider the above points can result in 
improper operation of the unit and possible damage to 
the installation. 

 

 

Отзывы: