Effective January 2019
10
Eaton SPD Series for Mounting External
to Electrical Distribution Equipment
Instruction Manual
IM01005031E - Rev. 6
3.2.2 Standard Feature Package
The Eaton SPD Series Standard Feature Package display is
shown in Figure 16
Figure 16. Standard Feature Package Display
The Standard Feature Package has the following features:
•
All features of the Basic Feature Package.
•
One Form C relay contact rated at 150Vac or 125Vdc @1A.
•
Normal operating conditions. N.O. = OPEN. N.C =
CLOSED.
•
Loss of protection on any phase or loss of power. N.O. =
CLOSED. N.C. = OPEN.
•
Audible alarm with Reset push button.
•
EMI/RFI filtering.
3.2.3 Standard With Surge Counter Feature Package
The Eaton SPD Series Standard With Surge Counter Feature
Package display is shown in Figure 17.
Figure 17. Standard With Surge Counter Feature Package
Display
The Standard With Surge Counter Feature Package has the fol-
lowing features:
•
All features of the Standard Feature Package.
•
LCD screen that displays surge count.
•
Reset button to RESET the surge counter to zero.
3.2.4 SPD Display Rotation
The SPD display can be rotated on the SPD enclosure, up to 360
degrees. This allows you to position the display for the best vis-
ibility regardless of the position in which the SPD is installed.
Rotations are at 90, 180, and 270 degrees.
Reposition the SPD display as follows:
1. Remove power from the unit.
2. Remove and discard the perforated overlay material at the
two opposite corners of the display.
3. Remove the two phillips head screws that hold the display.
4. Rotate the display to the desired position. Be careful not to
overstress the display ribbon cable.
5. Place the display back onto the SPD enclosure. Again, be
careful not to overstress or crimp the ribbon cable.
6. Replace the two phillips head screws. Tighten screws to
1.35 Nm (12 in-lbs).
7. Restore power to the unit.
3.3 IEC Approved Models
Eaton’s One-Port low-voltage Surge Protective Device Delta
Models SPD120480D3M, SPD160480D3M and SPD200480D3M
meet the requirements of IEC 61643-11 / EN 61643-11, Part 11:
Test Class II, and are intended to be installed in applications with
a degree of protection rated IP 20.
The Delta Models are intended for use with a 3 Phase TN-S
System with PE and Neutral Distribution, 5 conductor with a
minimum 10 AWG or 6 mm2. The Delta models are also intend-
ed for use with a 3 Phase TN-C System with PEN Distribution,
4 conductor with a minimum 10 AWG or 6 mm2. Screws used
for connection to ground shall be #10-32 x 3/8” and shall not be
zinc or aluminum. This product is not serviceable and contains
no replacement parts.
Additional product information and ratings for IEC Applications:
•
The SPD contains internal disconnects with a short circuit cur-
rent rating I
SCCR
of 200kA.
•
Residual Current IPE for this product is 5 mA.
•
Operating temperature is Normal -5°C to 40°C (23°F to
104°F).
•
Humidity range is 5% through 95% non-condensing.
•
The SPD may be mounted directly to earthed conductive sur-
face, installed as per this manual.
•
Temporary overvoltage rating UT = 402.6V.
•
Withstand or safe failure mode, t
T
= 120 minutes, U
T
= 526V.
•
Modes of protection as marked on a Delta SPD = L - L,
L -G(PE).