Eaton SPC Series Скачать руководство пользователя страница 7

7

Instruction Booklet 

IB158007EN

Effective September 2016

Installation instructions for Eaton SPC series 

surge protective device (SPD) 

  

EATON

 www.eaton.com

6 Operation

6.1 Power up and system checkout

Switch main panel power to ON and then switch SPC’s branch circuit 

breaker to ON .  One LED should light for each phase voltage being 

monitored .  Single phase electrical systems will light only one LED, 

split phase systems light two LEDs, and three phase systems will 

light all three LEDs .
If the connected LEDs do not light, remove power, check connec-

tions, and test again .  If the LEDs still do not light, contact your local 

authorized distributor or Power Quality Technical Resource Center at: 

1-800-809-2772, Option 4, sub-option 2, or email spd@eaton .com as 

the SPC may be damaged .

6.2 LED color states

The LED’s located on the lid of the SPC has three LED color states,

Green – fully protected
Yellow – loss of Neutral to Ground protection
Red – loss of phase protection

If the electrical system is single, split or 3 phase, the SPC will have 

either one, two or three green illuminated LEDs, respectively .  Each 

LED will illuminate when its associated phase voltage is present .
If any of these LEDs are yellow or red a problem may exist with 

incoming power, wiring, branch circuit breaker wiring or within the 

SPC itself .  Disconnect power, check connections and test again .  If 

the LEDs are still yellow or red, disconnect power to the SPC and 

contact your local authorized distributor or Power Quality Technical 

Resource Center at: 1-800-809-2772, Option 4, sub-option 2, or 

email spd@eaton .com as the SPC may be damaged .

6.3 Optionse: audible alarm and form C relay

otee:

N

Utilization of Form C contacts is optional .  Connection is not required 

for the proper operation of the SPC .

The audible alarm and Form C relay are tied to the Phase LED’s 

located on the SPC Series enclosure’s lid .  If protection to one or 

more phases is lost the following will occur: 

• 

Single, Split and 3 Phase devices - if all voltage is lost to the SPC 

then the green LED(s) will go out, the alarm will not sound and 

the relay will not be energized .

• 

Split and 3 Phase devices - if one phase voltage is lost to the SPC 

then that one green LED will go out, the alarm will not sound and 

the relay will stay energized (if there is another phase voltage 

present) .

• 

3 Phase Wye and 3 Phase High Leg Delta devices - if one or two 

phase voltages are lost to the SPC then one or two green LEDs 

will go out, the alarm will not sound and the relay will stay ener-

gized (if there is another phase voltage present) .

• 

3 Phase Delta – SPC needs at least 2 phases to energize the relay 

and to keep the alarm from sounding (if installed) .

• 

Single, Split and 3 Phase devices - if one or more LEDs turn red, 

the alarm will sound and the relay will de-energize .  

To silence 

the alarm, disconnect power to the SPC

 and contact your  

local authorized distributor or Power Quality Technical Resource 

Center at: 1-800-809-2772, Option 4, sub-option 2, or email  

spd@eaton .com as the SPC may be damaged .

otee:

N

Form C relay contacts are “fail safe” and only change state when 

power is applied to the SPC and the electrical system is operating normally or 

when loss of protection is detected and yellow or red LEDs are illuminated .

7 Specifications

kA per Phase

50, 80, 100, 120, 150, 160,  200

Nominal Discharge Current

20kA

Single Phase Voltages

120, 240, 277, 480

Split Phase Voltages

120/240

Wye System Voltages

120/208, 240/415, 277/480, 347/600

Delta System Voltages

240, 480, 600

High Leg Delta Voltage

240

Input Power Frequency

50/60 Hz

Protection Modes

Single Phase  L-N, N-G, L-G
Split Phase  L-N, N-G, L-G, L-L
Wye 

L-N, N-G, L-G, L-L

Delta 

L-G, L-L

High Leg 

L-N,N-G,L-G,L-L,H-N,H-G,H-L

Mounting feet Torque rating

20.3 lb-in (2.3 N

·

m)

Conduit locknut Torque rating

Not to exceed 200 lb-in (22.5 N

·

m)

Operating Temperature

-40°F to +140°F  (-40°C to +60°C)

Relative Humidity

5% - 95%, non condensing

Max. altitude

2000 m

Weight, vary per configuration

P1 enclosure ~2.5 lbs 

P2 enclosure ~4.0 lbs

Certification/Listing

UL 1449 4th edition, UL1283 6th edition, CSA 

269.1-14, 269.2-15, C22.2 No. 8-13 EMI Filter

SPD Type

UL1449 4th edition & CSA Type 1 and Type 

2 SPD

RoHS Compliant

Yes

Enclosure Rating

Type 4X Enclosure w/ mounting feet, IP56

Содержание SPC Series

Страница 1: ...es catalog number 3 3 SPC series product nameplate 3 4 Installation 3 5 Wiring diagrams 6 6 Operation 7 7 Specifications 7 8 Maintenance 8 9 Liability 8 10 Ordering guidelines 9 11 Voltage configurati...

Страница 2: ...rrent device Including branch panel loca tions and functions to protect sensitive electronic equipment from damaging voltage transients and surges The SPC should be installed as close as possible to t...

Страница 3: ...14 IN LENGTH TWISTED TOGETHER AND THEN BOUNDED AVOID USING 90 CONDUIT ELBOWS AND KEEP THE CONDUIT RUN AS SHORT AND STRAIGHT AS POSSIBLE SEE FIGURES 1 AND 2 WHEN MOUNTING THE SPD OUTDOORS USE WEATHERPR...

Страница 4: ...se as possible to the electrical panel using trade size conduit trade size coupling trade size connector and the supplied trade size conduit locknut Note N to maximize the SPC s performance 10 AWG wir...

Страница 5: ...uide are designed with internal overcur rent protection and do not require an external overcurrent protection device OCPD unless otherwise required by NEC UL and local electrical requirements to prote...

Страница 6: ...Code PHASE WIRE COLOR CODE PHASE WIRE COLOR L1 Phase A Black L2 Phase B Black L2 Phase B Hi Leg Delta Orange L3 Phase C Black Neutral White Ground Protected Earth Green w Yellow Stripe Figure 8 Single...

Страница 7: ...C then the green LED s will go out the alarm will not sound and the relay will not be energized Split and 3 Phase devices if one phase voltage is lost to the SPC then that one green LED will go out th...

Страница 8: ...t to terms and conditions outlined in appropriate Eaton selling policies or other contractual agreements between the parties This literature is not intended to and does not enlarge or add to any such...

Страница 9: ...ns 120N 120V Single Phase 2W G 240N 240V Single Phase 2W G 277N 277V Single Phase 2W G 480N 480V Single Phase 2W G 240S 120 240V Split Phase 3W G 240D 240V Delta 3W G 480D 480V Delta 3W G 600D 600V De...

Страница 10: ...r recommendations by Eaton shall not constitute any warranty by or impose any liability upon Eaton AND IS IN LIEU OF ANY AND ALL OTHER WARRANTIES EXPRESSED IMPLIED OR STATUTORY AS TO THE MERCHANTABILI...

Страница 11: ...11 Instruction Booklet IB158007EN Effective September 2016 Installation instructions for Eaton SPC series surge protective device SPD EATON www eaton com Notes...

Страница 12: ...re continuous therefore the specifications and information contained in this document may change without notice Eaton shall not be liable for errors contained herein or for incidental or consequential...

Отзывы: