background image

Pub 49440

Effective 01/02

3

Current Derating

Operation in ambient temperatures exceeding 40°C [104°F] is 
possible if the power dissipation is limited either by reducing 
the steady-state current or by reducing the duty cycle of the 
soft starter as shown in 

Table 6

.

Table 6. 

Current Derating  

Current Derating for S701_03N3S

Functional Diagram

Example 1

Start with initial torque controlled from the input.

Example 2

Soft start with kick start, initial torque.

Soft stop controlled from the mains input.

Utilization Categories (IEC 947-4-2)

Table 7. 

Utilization Categories

Wiring Directions

!

IMPORTANT

When using electrical or pneumatic tools for screw termi-
nals, observe maximum torque limits. 

Short Circuit Protection

Short circuit protection is divided into two levels — 
Type 1 and Type 2.

Type 1 — protects the installation
Type 2 — protects the installation and the 
semiconductors inside the motor controller

Short Circuit Protection by Circuit Breaker

A 3-phase motor with a correctly installed and adjusted over-
load relay will not short-circuit totally to earth or between the 3 
phases. Part of the winding will normally limit the short circuit 
current to a value that will cause instantaneous magnetic trip-
ping of the circuit breaker without damage to the soft starter. 
The magnetic trip response current is approximately 11 times 
the maximum adjustable current. 

Short Circuit Protection by Fuses

Type 1

S701_03N3S — protection max. 25A 

g

I/

g

L/

g

G

S701_15N3S — protection max. 50A 

g

I/

g

L/

g

G

S701_25N3S — protection max. 80A 

g

I/

g

L/

g

G 63A T

Type 2

S701_03N3S — protection max. l

2

t of the fuse 72A

2

S

S701_15N3S — protection max. l

2

t of the fuse 1800A

2

S

S701_25N3S — protection max. l

2

t of the fuse 6300A

2

S

NOTE: S701_25N3S

 — When protected by a non-time delay 

K5 or H class fuse rated 266% of motor FLA, this 
device is rated for use on a circuit capable of deliver-
ing not more than 5000 rms symmetrical amperes, 
600V maximum.

Ambient 
Temperature

S701_15N3S

S701_25N3S

40° to 50°C
[104° to 122°F]

12.5 Amps Continuous or 

15 Amps Max. on-time 15 

min. Max. duty cycle 0.8

20 Amps Continuous or 

25 Amps Max. on-time 15 

min. Max. duty cycle 0.8

50° to 60°C
[122° to 140°F]

10 Amps Continuous or 

15 Amps Max. on-time 15 

min. Max. duty cycle 0.65

17 Amps Continuous or 

25 Amps Max. on-time 15 

min. Max. duty cycle 0.65

Overload Trip Class

10A

10
20
30

15A
15A
12A
10A

25A
25A
20A
15A

Item

Specification

AC-52a

Control of slip-ring motor stators

AC-53a

Control of squirrel cage motor

AC-58a

Control of hermetic refrigerant compressors 
with automatic resetting of overload releases

S > 10mm,  I Max = 3,5 Amps
S < 10mm,  I Max = 2,5 Amps

S

Mains Ue L1, L2, L3

Control Ue A1A2

Motor Voltage

LED 1

LED 2

Example 1

Example 2

75°C

L1 T1 / L2 T2 / L3 T3

A1 A2 / 11 12

0.75 – 4 mm

2

[18 – 12 AWG]

0.5 – 1.5 mm

2

[20 – 16 AWG]

1.0 mm

2

[18 AWG]

0.5 – 0.75 mm

2

[20 – 18 AWG]

0.75 – 6 mm

2

[18 – 10 AWG]

0.5 – 1.5 mm

2

[20 – 16 AWG]

0.75 – 2.5 mm

2

[18 – 14 AWG]

0.5 – 1.5 mm

2

[20 – 16 AWG]

0.75 – 6 mm

2

[18 – 10 AWG]

0.5 – 1.5 mm

2

[20 – 16 AWG]

0.75 – 1.5 mm

2

[18 – 16 AWG]

0.5 – 1.5 mm

2

[20 – 16 AWG]

Posidrive 1
0.5 Nm max.
[4.4 lb-in max.]

N/A

4 mm
0.5 Nm max.
[4.4 lb-in max.]

3 mm
0.4 Nm max.
[3.5 lb-in max.]

* UL Tested.

*

*

*