Operation
Eaton 93PM Remote Monitoring Device (RMD) Installation and Operation Manual P-164000516—Rev 1
7
Figure 5. Display Screen Sections
Powering the RMD
To turn the RMD on press and hold the power pushbutton on the front of the RMD (see Figure 4) for three
seconds. The RMD should start with the Eaton logo being displayed. Then the power pushbutton on the front
of the RMD will illuminate green and the screen shown in Figure 5 should be displayed. If the display does not
start, let the battery charge for 30 minuets.
To turn the RMD off press and hold the power pushbutton on the front of the RMD for approximately
11 seconds.
If a white screen is displayed on the RMD after the UPS is turned on, press and hold the power pushbutton on
the front of the RMD for 15 seconds (while the power cable is plug in) and the RMD will subsequently establish
communication with the PXGMS card.
Silencing the Audible Alarm
To silence the audible alarm, press the power button momentarily.
NOTE
The PXGMS card must be setup and running in the UPS before starting the RMD. If
powered up together the RMP may not establish communication.
Status
Indicator
Icons
Information
Area