background image

 

 1 

©2015 Eaton Corporation 

All rights reserved 

REC Series Enclosure Installation Guide _issue 4 

Installation Guide  

 

 

 

 

 

REC Series Rack Installation Guide

 

Содержание REC Series

Страница 1: ...1 2015 Eaton Corporation All rights reserved REC Series Enclosure Installation Guide _issue 4 Installation Guide REC Series Rack Installation Guide...

Страница 2: ...4 Installation Guide REC Series Rack Installation Guide TABLE OF CONTENTS SECTION SAFETY WARNINGS 1 600 WIDE EXPLODED VIEW 2 800 WIDE EXPLODED VIEW 3 SWITCHING DOOR HANDING 4 STABILIZING 5 BAYING THE...

Страница 3: ...equipment may cause the enclosure to tip over 4 WARNING First load the heaviest electronic devices and accessories into the bottom of the enclosure to prevent the enclosure from becoming top heavy 5...

Страница 4: ...rporation All rights reserved REC Series Enclosure Installation Guide _issue 4 2 600 WIDE EXPLODED VIEW Installation Guide ITEM DESCRIPTION 1 Vented Door Assembly Option 2 Enclosure Frame 3 Roof Panel...

Страница 5: ...allation Guide _issue 4 Installation Guide 3 800 WIDE EXPLODED VIEW 5 6 6 ITEM DESCRIPTION 1 Vented Door Assembly Option 2 Double Vented Door Assembly Option 3 Enclosure Frame 4 Vented Door Assembly O...

Страница 6: ...tall the three hinge sections to the opposite side of enclosure frame Fig 2 4 Rotate the door 180 degrees 5 Re install the three hinge pins Fig 1 6 Loosen the two screws which secure the locking rods...

Страница 7: ...MPLEMENTED AND THE RACK MUST REMAIN STATIC IF THE RACK IS TO BE RELOCATED THEN EQUIPMENT MUST BE REMOVED BEFORE MOVING THE RACK Each enclosure is equipped with four leveling feet Fig 1 Use a 13 mm spa...

Страница 8: ...sure Fig 1 2 Position and level the adjacent enclosure frames Ensure that the frames are precisely aligned both vertically and front to back 3 Ensure a shake proof washer contacts the painted surface...

Страница 9: ...he side panel with the key supplied Fig 1 2 Tilt the panel to clear the upper flange 3 Lift the panel upwards to clear two locating pins Fig 2 Reinstall side panel 1 Align the two holes on the bottom...

Страница 10: ...osure Installation Guide _issue 4 Installation Guide 8 RACK MOUNT ADJUSTMENT 1 Loosen the four bolts using a 5mm Allen key do not remove the bolt Fig 1 2 Slide rails to desired location 3 Ensuring the...

Страница 11: ...ts note not all components used in every application ITEM REF DESCRIPTION LENGTH QUANTITY IMAGE 1 M6 x 25mm Zinc Plated Setscrew 25mm 4 2 M6 Shake proof Washer 8 3 M6 x 12mm Setscrew 4mm Allen 12mm 4...

Страница 12: ...itions M6 Thread forming screw M6 Shake proof washer Earth grounded cage nut M6 Shake proof washer M6 Thread forming screw The bolt together method for the rack frame ensures earth continuity of the r...

Страница 13: ...th bonding points to corner gussets adjacent to door hinge positions If double doors are fitted then fit main earth points to both adjacent corner gussets Note Main earthing points must be assembled s...

Страница 14: ...k STEP 3 19 INCH RAIL EARTH BONDING Remove the side panel to improve access Fit earth assembly as shown in Fig 3 0 and tighten assembly using a torque of M6 Plain washers X2 M6 Serrated hex flange M6...

Страница 15: ...the RH side panel to the rear corner gusset M6 Plain washers X2 M6 Serrated hex flange nut M6 Earth lead 350mm To doors Fig 6 0 M6 Plain washers X2 M6 Earth lead 500mm Fig 5 0 STEP 5 EARTH BONDING TO...

Страница 16: ...aisle shown for reference Fitting instructions follow same process but 1800mm wide aisles have wider side and roof panels TOOLS REQUIRED SPANNER WRENCH 8mm SPANNER WRENCH 10mm ALLEN KEY 5mm CROSS HEA...

Страница 17: ...served REC Series Enclosure Installation Guide _issue 4 Installation Guide Step 1 Ensure cabinets are aligned level and the correct distance apart either 1200mm or 1800mm depending on the aisle config...

Страница 18: ...mage right 13 12 Doors viewed from inside Master Door Slave Door 7 1 2 3 4 5 6 8 7 9 9 10 11 ITEM DESCRIPTION QTY 1 FRAME UPRIGHT LEFT 1 2 FRAME UPRIGHT RIGHT 1 3 CROSS BEAM 1 4 TOP PANEL 42U 1 5 TOP...

Страница 19: ...hown 10 12 Step 4 Fit the hinges item 9 to the frame uprights items 1 2 using M5 x 8mm screws item 10 shown in image below Note the hinges are handed Left or Right Fit hinges to corresponding door 42U...

Страница 20: ...L DOOR FRAME Installation Guide Step 6 Referring to images below offer up door frame to cabinets and attach using clamp plates item 11 and M6 x 16mm screws item 7 from inside the cabinets in 4 positio...

Страница 21: ...e frame and lifting them onto the hinge pins Note the door positions and panel gaps can be adjusted by loosening the hinge fixing screws and altering their relative positions The gap between the door...

Страница 22: ...aster door to be opened from inside the aisle To open the door from inside the aisle pull button while lifting latch refer to images below and push master door to the open position STEP 1 PULL Release...

Страница 23: ...ation visit www eaton eu electrical Eaton Industries Manufacturing GmbH Electrical Sector EMEA Route de la Longeraie 7 1110 Morges Switzerland Copyright 2012 All rights reserved Changes to the product...