6.1.1.2 BACnet MS/TP: Setting the MAC Address BACnet Network
Only 1 MAC address is set for ProtoAir regardless of how many light panels are connected to
ProtoAir.
Set the BACnet MS/TP MAC address of the ProtoAir to a value between 1 to 127 (MAC Master
Addresses); this is so that the BMS Front End can find the ProtoAir via BACnet discovery.
NOTE: Never set a BACnet MS/TP MAC Address from 128 to 255
. Addresses from 128 to 255 are
Slave Addresses and can not be discovered by BMS Front Ends that support auto discovery of
BACnet MS/TP devices.
Enter the following details into the web configuration as per
Device Instance
– Enter a range between 1 and 4,194,303 for the ProtoAir.
Name
– Enter a name for the ProtoAir.
Location
– Enter the location of the lighting panel.
Device Instance Offset
– Default of 50000 so that Device Instance begins at 50001.
Network Number
– Leave as default unless instructed by BMS integrator.
Baud Rate
– Enter a value of 9600, 19200, 38400, or 76800.
Figure 15: BACnet MS/TP Settings Window