84
Appendix D—Safety instructions for UL and cUL
POWERXL SERIES VFDS
MN040060EN—September 2020 www.eaton.com
Field wiring
•
The field installed conductors for this drive should be 75°C or higher copper wire.
•
The enclosure openings provided for conduit connections in the field shall be closed by UL Listed conduit fittings with
same type rating as the enclosure (Type 1).
Table 36. Connection sizes and torques
.
Output rating
Size and torque
Input voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
Power
wire size
AWG
(mm
2
)
Power wire
torque
in.-lb (N·m)
Ground
wire size
AWG
(mm
2
)
Ground
wire
torque
in.-lb (N·m)
Control
wire size
AWG (mm
2
)
Control
wire torque
in.-lb (N·m)
AI/DI
RO
100 Vac to
120 Vac
50/60 Hz
1-phase
FR1
DM1-111D6… 1.6
2.5
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-113D0… 3
4.8
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR2
DM1-114D8… 4.8
6.9
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-116D9… 6.9
7.8
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
200 Vac to
240 Vac
50/60 Hz
1-phase
FR1
DM1-121D6… 1.6
2.5
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-123D0… 3
4.8
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-124D8… 4.8
7.8
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR2
DM1-127D8… 7.8
11
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-12011… 11
17.5
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR3
DM1-12017… 17.5
25.3
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
200 Vac to
240 Vac
50/60 Hz
3-phase
FR1
DM1-321D6… 1.6
2.5
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-323D0… 3
4.8
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-324D8… 4.8
7.8
14 (2.5)
4.4 (0.5)
12 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-327D8… 7.8
11
12 (4)
4.4 (0.5)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR2
DM1-32011… 11
17.5
10 (6)
10.5 (1.2)
10 (6)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-32017… 17.5
25.3
8 (10)
10.5 (1.2)
10 (10)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR3
DM1-32025… 25.3
32.2
8 (10)
10.5 (1.2)
8 (10)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR4
DM1-32032… 32.2
48.3
4 (25)
33 (3.73)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-32048… 48.3
62.1
3 (35)
33 (3.73)
6 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
380 Vac to
480 Vac
50/60 Hz
3-phase
FR1
DM1-341D5… 1.5
2.2
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-342D2… 2.2
4.3
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-344D3… 4.3
5.6
14 (2.5)
4.4 (0.5)
14 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-345D6… 5.6
7.6
14 (2.5)
4.4 (0.5)
10 (2.5)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR2
DM1-347D6… 7.6
12
12 (4)
10.5 (1.2)
10 (4)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-34012… 12
16
10 (6)
10.5 (1.2)
10 (6)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-34016… 16
23
8 (10)
10.5 (1.2)
10 (10)
7.1 (0.8)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR3
DM1-34023..
23
31
8 (10)
10.5 (1.2)
8 (10)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR4
DM1-34031… 31
38
6 (16)
33 (3.73)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-34038… 38
46
4 (25)
33 (3.73)
8 (16)
14.2 (1.6)
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
525 Vac to
600 Vac
50/60 Hz
3-phase
FR2
DM1-354D5… 4.5
7.5
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-357D5… 7.5
10
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-35010… 10
13.5
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR3
DM1-35013… 13.5
18
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
FR4
DM1-35018… 18
22
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
DM1-35022… 22
27
28-16 (0.5-1.5) 1.73 (0.2)
4.5 (0.5)
Notes:
Line and motor cable size is selected according to UL 61800-5-1 for copper conductor rated 75°C. Use only with copper wire rated 75°C here. Size requirements for
other different wire types are defined in the National Electrical Code
®
, ANSI/NFPA
®
70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 61800-5-1.
If power cubes or bypass are used, a UL listed Class J, T, CF, CC or equivalent fuse is recommended.