Chapter 5—Electrical installation
POWERXL SERIES VFDS
MN040060EN—September 2020 www.eaton.com
Table 21. North America cable and fuse sizes
.
UL cable and fuse sizes
Output rating
Input rating
UL application
Input
voltage
Frame
size
Drive
catalog
number
CT/I
H
current
amps
VT/I
L
current
amps
CT/I
H
current
amps
VT/I
L
current
amps
Recom-
mended
fuse
(Class
J, T, CF,
or CC)
(max.
rating)
100
kAIC
Recom-
mended
miniature
inverse-
time
molded-
case
circuit
breaker
(max.
rating)
10/14
kAIC
Recom-
mended
type
E CMC
(max.
Rating)
65 kAIC
Recom-
mended
inverse-
time
molded-
case
circuit
breaker
(max.
rating)
100 kAIC
(Open type
only for
3-phase)
NEC
wire
size
line
and
motor
AWG
NEC
wire
size
ground
AWG
Terminal
size
line and
motor
AWG
Terminal
size
ground
AWG
380 Vac
to
480 Vac
50/60 Hz
3-phase
FR1
DM1-341D5…
1.5
2.2
1.8
2.6
6
4
XTPR
XTPAXLSA or
PKZM0-6.3 +
BK25/3-PKZ0-E
15
14
14
18-8
16-10
DM1-342D2… 2.2
4.3
2.6
5.2
10
8
XTPR
XTPAXLSA or
PKZM0-6.3 +
BK25/3-PKZ0-E
15
14
14
18-8
16-10
DM1-344D3… 4.3
5.6
5.2
6.7
15
10
XTPR
XTPAXLSA or
PKZM0-10 +
BK25/3-PKZ0-E
15
14
14
18-8
16-10
DM1-345D6… 5.6
7.6
6.7
9.1
30
15
XTPR
XTPAXLSA or
PKZM0-10 +
BK25/3-PKZ0-E
15
14
10
18-8
16-10
FR2
DM1-347D6… 7.6
12
9.1
14.4
30
20
XTPR
XTPAXLSAD or
PKZM4-16 +
BK50/3-PKZ4-E
20
12
10
20-6
12-8
DM1-34012…
12
16
14.4
19.2
40
25
XTPR
XTPAXLSAD or
PKZM4-25 +
BK50/3-PKZ4-E
30
10
10
20-6
12-8
DM1-34016…
16
23
19.2
27.6
60
32
XTPR
XTPAXLSAD or
PKZM4-32 +
BK50/3-PKZ4-E
40
8
10
20-6
12-8
FR3
DM1-34023..
23
31
26.5
35.7
70
\
XTPR
XTPAXLSAD or
PKZM4-40 +
BK50/3-PKZ4-E
50
8
8
20-6
10-8
FR4
DM1-34031…
31
38
35.7
43.7
70
\
XTPR
XTPAXLSAD or
PKZM4-50 +
BK50/3-PKZ4-E
70
6
8
20-2
8-6
DM1-34038…
38
46
43.7
52.9
80
\
XTPR
XTPAXLSAD or
PKZM4-58 +
BK50/3-PKZ4-E
80
4
8
20-2
8-6
525 Vac
to
600 Vac
50/60 Hz
3-phase
FR2
DM1-354D5… 4.5
7.5
DM1-357D5… 7.5
10
DM1-35010…
10
13.5
FR3
DM1-35013…
13.5
18
FR4
DM1-35018…
18
22
DM1-35022…
22
27
Notes:
Can be any UL listed type with below ratings.
Due to UL listing, only can be below Eaton types.
Line and motor cable size is selected according to UL 61800-5-1 for copper conductor rated 75°C. Use only with copper wire rated 75°C here. Size requirements for
other different wire types are defined in the National Electrical Code
®
, ANSI/NFPA
®
70.
Earthing conductor size is determined by the maximum overcurrent device rating used ahead of the drive according to UL 61800-5-1.
n
If power cubes or bypass are used, a UL listed Class J, T, CF, CC or equivalent fuse is recommended.
Refer to Appendix B for specific branch circuit protection devices types recommended by Eaton.
(continued).