User’s and Installation Guide 

42

4.2 Modes

The Powerware 9395E UPS supports a critical load in three different modes of operation. The UPS 
can automatically use all three modes, as required. The standard operation modes are:

In Normal mode, the critical load is supplied by the inverter, which derives its power from 

• 

rectified utility AC power. In this mode, the battery charger also provides charging current 
for the battery, if needed.
In Battery mode, the battery provides DC power, which maintains inverter operation. The 

• 

battery supports the critical load.
In Bypass mode, the critical load is directly supported by utility power. The following 

• 

paragraphs describe the differences in the three UPS operating modes, using block 
diagrams to show the power flow during each mode of operation.

4.2.1 Normal mode

Figure 4-2 shows the path of electrical power through the UPS system when the UPS is 
operating in normal mode.

Figure 4-2. Path of current through the UPS in normal mode

During normal UPS operation, power for the system is derived from a utility input source 
through the rectifier input contactor K1. The front panel displays “Normal,” indicating the 
incoming power is within voltage and frequency acceptance windows. Three-phase AC input 
power is converted to DC using IGBT devices to produce a regulated DC voltage to the inverter. 
The battery is charged directly from the regulated rectifier output through a buck or boost DC 
converter, depending on whether the system voltage and the size of the battery string attached 
to the unit. 

The battery converter derives its input from the regulated DC output of the rectifier and 
provides either a boosted or bucked regulated DC voltage charge current to the battery. The 
battery is always connected to the UPS and ready to support the inverter should the utility input 
become unavailable.

UPS 200 kVA 

Содержание Powerware 9395E

Страница 1: ...Powerware 9395E UPS 200 kVA User s and Installation Guide...

Страница 2: ...ial and industrial application in the second environment Installation restrictions or additional measures may be needed to prevent disturbances 2010 Eaton Corporation All Rights Reserved The contents...

Страница 3: ...n information 21 3 2 Unloading the UPS cabinet from the pallet and mechanical installation 21 3 3 Battery cabinet installation 23 3 4 Installing UPS external and battery power wiring 25 3 4 1 External...

Страница 4: ...indicators 66 6 4 System event messages 66 7 Communication 67 7 1 X Slot cards 67 7 2 Powerware LanSafe Power Management Software 68 7 3 Terminal mode 68 7 3 1 Display UPS control panel 68 7 3 2 Even...

Страница 5: ...erruptions batteries provide emergency power to safeguard operation The UPS system is housed in a single free standing cabinet with safety shields behind the door for hazardous voltage protection The...

Страница 6: ...UPS 200 kVA User s and Installation Guide 6 Figure 1 1 Powerware 9395E 200 cabinet...

Страница 7: ...ing and inverter ripple currents Charging at high currents can overheat and damage batteries 1 1 4 Power Management Software Powerware LanSafe Power Management Software is bundled as part of the Softw...

Страница 8: ...al should be read At a minimum Chapters 1 through 3 and Chapter 5 should be examined Read through each procedure before beginning the procedure Perform only those procedures that apply to the UPS syst...

Страница 9: ...at you should not discard waste electrical or electronic equipment WEEE in the trash For proper disposal contact your local recycling reuse or hazardous waste center 1 7 For more information Refer to...

Страница 10: ...the procedures and illustrations in the paragraph 2 2 and Chapter 3 to create a logical plan for installing the system 2 2 Preparing the site For the UPS system to operate at peak efficiency the inst...

Страница 11: ...From front of cabinet 915 mm working space From back of cabinet 100mm From right side of cabinet None required but for easier service 500 mm is recommended From left side of cabinet None required Tabl...

Страница 12: ...UPS 200 kVA User s and Installation Guide 12 Figure 2 1 UPS cabinet dimensions front view Figure 2 2 UPS cabinet dimensions right side view...

Страница 13: ...UPS 200kVA User s and Installation Guide 13 Figure 2 3 UPS cabinet dimensions top view Figure 2 4 UPS cabinet dimensions bottom view Front...

Страница 14: ...If installing as part of the UPS system a maintenance bypass without a rectifier input breaker a minimum of two separate feeds with upstream feeder breakers or one feed with two upstream feeder breake...

Страница 15: ...nd D map to figure 6 5 on page 6 6 Table 2 4 Input output ratings and external wiring requirements for the Powerware 9395E 200 Read and understand the following notes while planning and performing the...

Страница 16: ...tomer ground Ground Ground 7 1 bolt mounting 22 M10 NOTE Customer ground size1 0 can be run in any conduit Table 2 5 UPS cabinet power cable terminations for the Powerware 9395E 200 Part Size Quantity...

Страница 17: ...ies are remotely located The battery disconnect switch should be installed between the battery and the UPS External DC input overcurrent protection and disconnect switch for the remote battery locatio...

Страница 18: ...larms can be programmed to display the alarm functional name LAN and telephone drops for use with X Slot cards must be provided by facility planners or the customer The UPS Battery Aux and 48 Vdc Shun...

Страница 19: ...verify that the forklift or pallet jack is rated to handle the weight of the cabinet seeTable 2 1 on page 11 for cabinet weight 2 Use a forklift or pallet jack to move the packaged cabinet to the ins...

Страница 20: ...nd compare each item with the Bill of Lading If damage has occurred or shortages are evident contact your service representative immediately to determine the extent of the damage and its impact upon f...

Страница 21: ...abinet is bolted to a wooden pallet supported by wood skids To remove the pallet and mechanically install the UPS perform the following procedure NOTE When a line up and match UPS system is ordered to...

Страница 22: ...for later use 3 Remove the three bolts securing the right side shipping bracket to the cabinet and three bolts securing the bracket to the pallet see Figure 3 2 Remove the front shipping bracket If i...

Страница 23: ...UPS 200 kVA User s and Installation Guide 23 Figure 3 1 Removing left side shipping bracket...

Страница 24: ...ight side shipping bracket 3 3 Battery cabinet installation To install the battery cabinet refer to the Powerware 9395 Integrated Battery Cabinet Model IBC L installation manual After the battery cabi...

Страница 25: ...power wiring 3 4 1 External power wiring installation To install wiring to connections 1 Remove one top screw and two bottom screws securing the UPS left front panel see Figure 3 1 Lift the panel str...

Страница 26: ...UPS 400 kVA 2x200 kVA User s and Installation Guide 26 Figure 3 3 Conduit and wire entry locations...

Страница 27: ...UPS 200 kVA User s and Installation Guide 27 Figure 3 4 a UPS power terminal locations Figure 3 4 b UPS power terminal locations Front view Side view...

Страница 28: ...UPS 200 kVA User s and Installation Guide 28 Figure 3 5 a front view Figure 3 5 b side view UPS power terminal locations MBS version...

Страница 29: ...Step 7 5 Route and connect the battery cables between the UPS and the battery system See Figure 3 3 through Figure 3 5 for wiring access information and terminal locations 6 Connect the positive negat...

Страница 30: ...plates WARNING Do not directly connect relay contacts to the mains related circuits Reinforced insulation to the mains is required 7 To locate the appropriate terminals and review the wiring and termi...

Страница 31: ...User s and Installation Guide 31 Figure 3 7 Interface terminal locations UPS 200 kVA...

Страница 32: ...2 Building alarm 1 return 3 Building alarm 2 Programmable UPS alarm Activated by a remote dry contact closure 4 Building alarm 2 return 5 Building alarm 3 Programmable UPS alarm Activated by a remote...

Страница 33: ...as shown Building alarm inputs can be programmed for use with either normally open or normally closed contacts All control wiring and relay and switch contacts are customer supplied NOTEThe building a...

Страница 34: ...see paragraph 2 2 2 on page 14 Table 3 1 and Figure 3 7 through Figure 3 10 6 If battery cabinets are installed attached to the UPS cabinet proceed to Step 7 if battery cabinets are installed separat...

Страница 35: ...install the LAN and telephone drops 2 If not already accomplished remove one top screw and two bottom screws securing the UPS center front panel see Figure 3 1 Lift the panel straight up to remove fr...

Страница 36: ...itch not tied into any other circuits NOTE This procedure is intended to be used for the installation of the Powerware remote EPO switch If installing another manufacturer s switch only use this proce...

Страница 37: ...screws securing the small top internal safety shield panel and remove the panel This panel is to the right of the X Slot communication bays see Figure 3 7 on page 30 5 Remove the UPS cabinet interface...

Страница 38: ...erminals 6 and 7 of the remote EPO switch as shown in Figure 3 12 Remote EPO switch wiring must be in accordance with UL Class II requirements 12 When all wiring is complete reinstall the small top in...

Страница 39: ...stallation checklist This checklist ensures that you have completely installed all hardware cables and other equipment Complete all items listed on the checklist to ensure a smooth installation Make a...

Страница 40: ...nstalled UPS system is clean and dust free It is recommended that the UPS be installed on a level floor suitable for computer or electronic equipment r Adequate workspace exists around the UPS and oth...

Страница 41: ...nterrupted or falls outside the parameters specified in Chapter 10 Product specifications the UPS uses a backup battery supply to maintain power to the critical load for a specified period of time or...

Страница 42: ...path of electrical power through the UPS system when the UPS is operating in normal mode Figure 4 2 Path of current through the UPS in normal mode During normal UPS operation power for the system is...

Страница 43: ...becomes overloaded or unavailable the UPS switches to Bypass mode The UPS automatically returns to Normal mode when the overload condition is cleared and system operation is restored within specified...

Страница 44: ...static switch is rated as a continuous duty devfice that fis used any tfime the finverter is unable to support the applied load The statfic swfitch befing an eflectronficaflfly controflfled device can...

Страница 45: ...ter output can no longer support the connected loads When this event occurs the UPS fissues another set of audible and visual alarms indicating SHUTDOWN IMMINENT Unless the rectfiffier has a valid AC...

Страница 46: ...If the load does not require a neutral and there is no neutral conductor connected at the bypass input a neutral to ground bonding jumper must be installed DO NOT install both a source neutral and a b...

Страница 47: ...minimum of two separate feeds with upstream feeder breakers or one feed with two upstream feeder breakers must be provided one for the UPS and one for the maintenance bypass input DO NOT use one feed...

Страница 48: ...iminary startup verifies all electrical interconnections to ensure the installation was successful and the system operates properly NOTE Read this section of the manual and have thorough knowledge of...

Страница 49: ...1 shows the UPS controls and indicators Figure 5 1 Powerware 9395E 200 kVA UPS controls and indicators 5 1 1 Control panel The Control Panel is used to set up and control the UPS and to monitor UPS o...

Страница 50: ...njunction with the alarm horn to let you know the operating status of the UPS TheTable 5 1 shows the status indicators and provides a functional description Indicator Status Descritions Green On The U...

Страница 51: ...more information about alarms and notices see Chapter 6 Responding to system events B The information area contains data about UPS status and operations C The menu bar lists the titles of the availab...

Страница 52: ...etting Up or down arrows scroll through screens and lists or highlight settings Left or right arrows select or adjust settings displayed on the screen Table 5 2 Display function menu map 5 2 4 Mimic s...

Страница 53: ...he unit is on battery The screen displays the total number of times since the last log reset that the unit has transferred to battery It also displays the date of the last log reset the average time s...

Страница 54: ...ni tored Save The Time Interval Monitored Setup Save screen lets you save the new time interval retry another time interval or abort the change Press SAVE RETRY or ABORT If SAVE or ABORT is pressed th...

Страница 55: ...from the Maximum Current Log Setup screen 2 menu to display the Time Interval Moni tored Setup screen Use the left or right arrow pushbuttons to select the char acter position Use the up or down arrow...

Страница 56: ...ress the DONE pushbutton The System Setup Level 1 menu screen is displayed The default password is L1 Function Selection Use the up or down arrow pushbuttons to highlight the setup function screen des...

Страница 57: ...reen is used to change and save the settings for the selected serial communication port The COM port number selected from the COM Port Setup screen displays If the changes are not wanted use the ABORT...

Страница 58: ...ailed information about using the LOAD OFF and shutdown screens see Chapter 5 UPS operating instructions Figure 5 7 Load off screen 5 3 Operation 5 3 1 Starting the UPS in normal mode To start the UPS...

Страница 59: ...er is now supplied to the Critical load in Normal mode It takes approximately 1 minute for the UPS to achieve Normal mode 11 The UPS is now operating in Normal mode and the NORMAL status indicator is...

Страница 60: ...PM status line DC STARTIN INVERTER STARTING INVERTER SYNCING READY The rectifier and inverter turn on When the inverter reaches full voltage the UPS is ready to transfer to the normal mode and supply...

Страница 61: ...e System Control screen appears 3 Press the pushbutton to display System Controls Screen 2 4 Press the PM OFF pushbutton on the System Controls menu bar The power module PM status indicates SHUTDOWN T...

Страница 62: ...off until restarted To use the LOAD OFF pushbutton 1 Press the LOAD OFF pushbutton The Load Off screen appears providing a choice to proceed or abort the shutdown CAUTION All power to the critical lo...

Страница 63: ...e the critical load NOTE The following instructions are for the Eaton Corporation supplied REPO switch If a customer supplied REPO switch is used it may not activate in the same manner refer to the op...

Страница 64: ...cated in the site wiring Turn UPS from normal mode to mechanical bypass The procedure to turn the UPS to mechanical bypass switch is described below 1 The normal start position should be following 2 P...

Страница 65: ...rectifier input to UPS 3 Turn ON Static bypass switch to connect bypass input to UPS 4 Perform UPS start up procedure bypass mode contained in paragraph 5 3 2 5 Turn S10 switch from bypass position to...

Страница 66: ...ndicators The status indicators on the UPS control panel and the event horn let you know when the UPS system is operating in any mode other than Normal Only the Normal indicator is visible during norm...

Страница 67: ...rk management system NMS using SNMP connects to a twisted pair Ethernet 10 100BaseT network It has a built in switching hub that allows three additional network devices to be connected to the network...

Страница 68: ...l panel When this function is invoked a facsimile of the UPS control panel is displayed on the terminal screen All controls are functional and can control the UPS remotely The only exception is the Lo...

Страница 69: ...SERIAL MCU DSP 70 81 14 MCU BOOTLOADER 80 40 MCU PLD 1 00 PMF 1 DSP 80 81 14 PMF 1 BOOTLOADER 80 40 PMF 1 PLD 1 00 XSLOT CAN BRIDGE 0 00 CSB DSP 70 81 14 CSB BOOTLOADER 1 12 DISPLAY 1 06 TIME 19 17 1...

Страница 70: ...ne general purpose relay contact is provided as a standard feature on the UPS The alarm contact is located inside the UPS on the customer interface terminal board You can use a normally closed or norm...

Страница 71: ...oved Do not make any assumptions about the electrical state of any cabinet in the UPS system Since each battery string is an energy source in itself opening the battery circuit breaker does not de ene...

Страница 72: ...doors and wash or replace as necessary The left ISBM filter size is 12 20 1 and the right UPM filter sizes are 19 5 21 5 0 5 Contact your service representative for replacement filters To remove the...

Страница 73: ...ste electrical or electronic equipment in the trash For proper disposal contact your local collecting recycling reuse or hazardous waste center and follow the local legislation These symbols indicate...

Страница 74: ...98 Line Surges 6 kV OC 3 kA SC per ANSI 62 41 and IEC 801 4 Battery Voltage 480 Vdc 10 2 2 UPS system output UPS Output Capacity 100 rated current Output Voltage Regulation 1 10 to 100 load Output Vo...