User’s and Installation Guide
35
NOTE Battery Aux and DC Shunt Trip wiring should be a minimum of 1.5 mm
2
.
Figure 3-10. Typical battery interface connection
3.5.3 X-Slot connections
NOTE
LAN and telephone drops for use with X-Slot cards must be provided by the customer.
NOTE
When installing internal wiring to X-Slot terminals, route the wiring through the internal
opening in the X-Slot communication bay.
For installation and setup of an X-Slot card, please contact Eaton Corporation.
To install wiring to connections:
1. If not already installed, install the LAN and telephone drops.
2. If not already accomplished, remove one top screw and two bottom screws securing the
UPS center front panel (see Figure 3-1). Lift the panel straight up to remove from the panel
hanger bracket at the top of the cabinet.
3. Remove the UPS cabinet interface entry plates to drill or punch holes (see Figure 3-3 on
page 26).
4. Reinstall the interface entry plates.
5. Route and install the LAN, telephone, and other cables to the appropriate X-Slot cards. See
Figure 3-7 and Figure 3-11 for X-Slot location.
6. When all wiring is complete, reinstall the front panel removed in previous steps and secure
with the retained hardware.
7. Refer to the manual supplied with the X-Slot card for operator instructions.
UPS 200 kVA
Содержание Powerware 9395E
Страница 1: ...Powerware 9395E UPS 200 kVA User s and Installation Guide...
Страница 6: ...UPS 200 kVA User s and Installation Guide 6 Figure 1 1 Powerware 9395E 200 cabinet...
Страница 23: ...UPS 200 kVA User s and Installation Guide 23 Figure 3 1 Removing left side shipping bracket...
Страница 26: ...UPS 400 kVA 2x200 kVA User s and Installation Guide 26 Figure 3 3 Conduit and wire entry locations...
Страница 31: ...User s and Installation Guide 31 Figure 3 7 Interface terminal locations UPS 200 kVA...
Страница 76: ......