15
4. Implementation Table
PXM 4/6/8K DNP3 Ethernet Communications User Manual
MN150005EN January 2017 www.eaton.com
Object
REQUEST
Master May Issue
Outstation Must Parse
RESPONSE
Master Must Parse
Outstation May Issue
Object
Number
Variation
Number
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function Codes
(dec)
Qualifier Codes (hex)
34
0
Analog Input Dead band (Variation 0 is
used to request default variation)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
34
1
16 bit Analog Input Dead band
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –see
note 2)
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
34
2 (default –
see note 1)
32 bit Analog Input Deadband
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –see
note 2)
2 (write)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
40
0
Analog Output Status
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
40
1
32-Bit Analog Output Status
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –see
note 2)
40
2 (default –
see note 1
16-Bit Analog Output Status
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –see
note 2)
40
3
Short floating point Analog Output
Status
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
17, 28 (index –see
note 2)
50
0
Time and Date
50
1 (default –
see note 1
Time and Date
1 (read)
07, (limited qty = 1)
129 (response)
07 (limited qty = 1)
2 (write)
07, (limited qty = 1)
60
1
Class 0 Data
1 (read)
06 (no range, or all)
60
2
Class 1 Data
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
3
Class 2 Data
1 (read)
06 (no range, or all)
07, 08 (limited qty)
60
4
Class 3 Data
1 (read)
06 (no range, or all)
07, 08 (limited qty)
80
1
Internal Indications
1 (read)
00, 01 (start-stop)
129 (response)
00, 01 (start-stop)
Note 1: A default variation refers to the variation responded when variation 0 is requested and/or in class 0, 1, 2, or 3 scans. Default variations are configurable; however, default set-
tings for the configuration parameters are indicated in the table above.
Note 2: For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests
sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01. (For change-event objects, qualifiers 17 or 28 are always responded.)
Note 3: Writes of Internal Indications are only supported for index 4 or 7 (Need Time IIN1-4 or Restart IIN1-7)