MIB Files
Eaton Power Xpert Gateway PXGX UPS Card User’s Guide 164202123—Rev 1
55
Powerware UPS MIB
Note:
Not every UPS model implements all of the Powerware UPS MIB objects. For example, the Bypass
objects are supported only by larger UPSs with a separate bypass feed.
The Powerware UPS MIB consists of the following groups:
l
Identification – the xupsIdent status objects provide UPS information, such as the UPS model or UPS
firmware version.
l
Battery – the xupsBattery status objects provide UPS battery information, such as battery time remaining or
the percentage of battery charge.
l
Input, Output, and Bypass – the xupsInput, xupsOutput, and xupsBypass status objects allow the network
manager to check or graph the condition of the UPS and its environment, such as monitoring input voltage
and output load.
l
Environment – the xupsEnvironment objects provide data around the UPS, such as the ambient
temperature, and also allow you to set the upper and lower limits for the ambient temperature alarm.
l
Alarms and Traps – the xupsAlarm and xupsTrapControl objects alert the SNMP management station to the
condition of the UPS and of significant conditions, such as Shutdown Imminent.
l
Test – the xupsTest objects perform a general UPS systems test and UPS battery test.
l
Control – with the xupsControl objects, a network manager can remotely control the UPS by SNMP set
commands, performing such tasks as shutting down or turning on the UPS.
l
Configuration – the xupsConfig objects allow you to view UPS configuration, such as watts, voltage, or
frequency and configure the UPS date and time and installation date.
l
Receptacle – the xupsRecep objects provide status information about the controllable load groups and
control objects for removing and returning power to these load groups.
l
Topology – the xupsTopology objects describe the machine type and are primarily used for
machine-to-machine communication within a power management system.
RFC 1628 UPS MIB
The RFC 1628 standard UPS MIB consists of the following groups:
l
Identification – the upsIdent status objects provide UPS information, such as the UPS model or UPS
firmware version.
l
Battery – the upsBattery status objects provide UPS battery information, such as battery time remaining or
the percentage of battery charge.
l
Input, Output, and Bypass – the upsInput, upsOutput, and upsBypass status objects allow the network
manager to check or graph the condition of the UPS and its environment, such as monitoring input voltage
and output load.
l
Alarms – the upsAlarm objects alert the SNMP management station to the condition of the UPS and of
significant conditions, such as Shutdown Imminent; this group also lists well-known UPS alarm conditions.
l
Test – the upsTest objects perform UPS diagnostic testing and provide the test results; this group also lists
well-known UPS diagnostic tests.
l
Control – with the upsControl objects, a network manager can remotely control the UPS by SNMP set
commands, performing such tasks as shutting down or turning on the UPS.
l
Configuration – the upsConfig objects allow you to view UPS configuration, such as watts, voltage, or
frequency; for UPSs that allow read-write control for objects in this group, you can also remotely configure
UPS parameters, such as input voltage or output frequency.