Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
99..22
P
Peerrffoorrm
miinngg P
Prreevveennttiivvee M
Maaiinntteennaannccee
The UPS system requires very little preventive maintenance. However, the system should be inspected
periodically to verify that the units are operating normally and that the batteries are in good condition.
99..22..11
D
DA
AIILLYY M
Maaiinntteennaannccee
Perform the following steps daily:
1.
Check the area surrounding the UPS system. Ensure the area is not cluttered, allowing free access to the
unit.
2.
Ensure the air intakes (vents on the front door or panels) and the exhaust openings (on top of the PM
section) are not blocked.
3.
Ensure the operating environment is within the parameters specified in paragraph
Environmental and Installation Considerations
and
.
4.
Ensure the UPS is in Normal mode (Normal status indicator is illuminated). If an alarm lamp is illuminated
or the Normal status indicator is not illuminated, contact an Eaton service representative.
99..22..22
M
MO
ON
NTTH
HLLYY M
Maaiinntteennaannccee
Perform the following steps monthly:
1.
Monitor system parameters as described in paragraph
or
Using the Color Touchscreen Control Panel
2.
Check the UPS air filters (located behind the front panels or door) and wash or replace as necessary. See
and
or
for filter locations, and
for filter sizes. Contact an Eaton
service representative for replacement filters.
To remove and replace the filters:
Table 42. UPS Filter Sizes
Filter Location
Size
Bottom Left ISBM Section Air Filters (Continuous Static Switch)
12" x 20" x 0.25"
Bottom Right ISBM Section Air Filters (Continuous Static Switch)
12" x 20" x 0.25"
Middle Right ISBM Section Air Filter (Continuous Static Switch)
20” X 6.3” X 0.5”
UPM Section Air Filters
20" x 44" x 0.25"
Verify washed filters are thoroughly dry before reinstalling.
a.
Remove one top screw and two bottom screws securing each PM section front panel (see
Lift the panel straight up to remove it from the panel hanger bracket at the top of the cabinet.
b.
Remove one top screw and two bottom screws securing each ISBM section front panel (see
). Lift the panel straight up to remove it from the panel hanger bracket at the top of the
cabinet.
c.
If the UPS is a continuous static switch configuration, unfasten the front door latch and swing the door
open (see
d.
Pull the foam filters over the screw heads on the cabinet mounted studs and remove the filters from
the cabinet.
Содержание Power Xpert 9395
Страница 8: ......
Страница 20: ...xx Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 List of Figures ...
Страница 37: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Safety Warnings ...
Страница 137: ...114 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Installing Options and Accessories ...
Страница 175: ...152 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Understanding UPS Operation ...
Страница 249: ...226 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Operating Instructions ...
Страница 257: ...234 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Communication ...
Страница 265: ...242 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Maintenance ...
Страница 268: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 245 Product Specifications ...
Страница 269: ...16420172515 164201725 15 ...