Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
227
C
Chhaapptteerr 88 C
Coom
mm
muunniiccaattiioonn
This chapter describes the communication features of the Power Xpert 9395 UPS and provides information
about connecting hardware and using Terminal mode. For terminal wiring information, see paragraph
UPS System Interface Wiring Preparation
and paragraph
Installing Interface Connections
. For location
of the customer interface panels and terminals, see
and
through
.
88..11
X
X--S
Slloott C
Caarrddss
The Power Xpert
©
9395 UPS has four standard, factory-installed X-Slot communication bays. See
for
bay locations. The UPS is compatible with the following X-Slot cards (see
•
Power Xpert Gateway Card. provides a data gateway from the UPS to the Power Xpert software; provides
remote monitoring through a Web browser interface, e-mail, and a network management system using
SNMP; connects to a twisted-pair Ethernet (10/100BaseT) network. Modbus TCP support provides direct
integration of the UPS parameters to a Building Management System (BMS). It has a built-in switching hub
that allows one additional network device to be connected to the network without the requirement of an
additional network drop.
•
Modbus Card . provides direct integration of UPS information (meters and status) to a Building
Management System (BMS) using the Modbus RTU protocol.
•
Relay Interface Card (AS/400). has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure,
Low battery, UPS alarm/OK, or On bypass when interfacing with IBM AS/400 computers, other relay
connected computers, and industrial applications.
•
Industrial Relay Card (IRC). indicates the operating status of the UPS system using the customer's
monitoring equipment. The IRC uses four isolated normally-open or normally-closed dry relay contacts to
indicate the UPS status. Online, Bypass, Battery, and Alarm modes can be monitored.
•
Powerware Hot Sync CAN Bridge Card. provides connectivity for operational mode control and metering of
a parallel system at any UPM in the system. In addition, this card can be used to connect optional system
monitoring devices, such as a Remote Monitor Panel II (RMP II), a Relay Interface Module II (RIM II), or a
Supervisory Contact Module II (SCM II) to the UPS. LAN drops for use with X-Slot connectivity cards must
be provided by facility planners or the customer.
LAN and telephone drops for use with X-Slot connectivity cards must be provided by facility planners or the
customer.
For installation and setup of an X-Slot card, contact an Eaton service representative (see
).
Refer to the manual supplied with the X-Slot card for user instructions.
Figure 147. Optional X-Slot Cards
Relay Interface Card
Modbus Card
Powerware Hot Sync
CAN Bridge Card
Industrial Relay Card
Power Xpert Gateway Card
Содержание Power Xpert 9395
Страница 8: ......
Страница 20: ...xx Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 List of Figures ...
Страница 37: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Safety Warnings ...
Страница 137: ...114 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Installing Options and Accessories ...
Страница 175: ...152 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Understanding UPS Operation ...
Страница 249: ...226 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Operating Instructions ...
Страница 257: ...234 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 Communication ...
Страница 265: ...242 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 UPS Maintenance ...
Страница 268: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725 Rev 15 245 Product Specifications ...
Страница 269: ...16420172515 164201725 15 ...