136
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716—Rev 13
13. Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM status indicates SHUTDOWN. The power module is turned off. The remaining UPMs continue to
supply the critical load.
Logic power remains on.
77..33..2211 S
Siinnggllee U
UP
PM
M R
Reessttaarrtt
To restart a single UPM from a shutdown state:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
If UPM 4 (FI-UPM) is installed, proceed to Step 3; otherwise, proceed to Step 7.
3.
On the System Status screen, select the
UPM
command. The UPS Control Command screen screen is
displayed.
4.
On the UPS Control Command screen, select the UPM to restart.
5.
Press the
CONTROLS
pushbutton on the UPS Control Command menu bar. The UPM Control Command
screen is displayed.
6.
Proceed to Step 9.
7.
On the System Status screen, select the
UPM
command.
8.
Press the
CONTROLS
pushbutton on the System Status Command menu bar. The UPM 1 Control
Command screen is displayed.
9.
On the UPM Control Command screen, select
UPM ON
.
10. Press the
SELECT
pushbutton on the UPM Command menu bar.
11. Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM rectifier and inverter turn on.
12. To transfer the UPM to Online mode, press the
CONTROLS
pushbutton on the UPS Control Command
menu bar. The UPM Control Command screen is displayed.
13. On the UPM Control Command screen, select
UPM GO TO ONLINE
.
14. Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM transfers to Online mode. The UPM status indicates
ONLINE
.
77..33..2222 U
UP
PS
S aanndd C
Crriittiiccaall LLooaadd S
Shhuuttddoow
wnn
To perform maintenance or service on the critical load, shut down power to the load:
1.
Turn off all equipment that is being powered by the UPS.
2.
Perform the LOAD OFF procedure in paragraph
Using the UPS LOAD OFF Pushbutton or Command
.
The input, output, battery, and bypass backfeed contactors open, and the power module is turned off.
Содержание Power Xpert 9395 550
Страница 1: ...p n 164201716 Revision 13 225 550 kVA Installation and Operation Manual Power Xpert 9395 550 275 UPS...
Страница 8: ......
Страница 18: ...xviii Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716 Rev 13 List of Figures...
Страница 31: ...10 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716 Rev 13 Introduction...
Страница 35: ...14 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716 Rev 13 Safety Warnings...
Страница 133: ...112 Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716 Rev 13 Understanding UPS Operation...
Страница 220: ...Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201716 Rev 13 199 Product Specifications...
Страница 221: ...16420171613 164201716 13...