background image

Read and retain for
future reference

Pow-R-Line

®

3FQS

Fusible Panelboard

Instruction Leaflet

E3A1071 RevG

Содержание Pow-R-Line 3FQS

Страница 1: ...Read and retain for future reference Pow R Line 3FQS Fusible Panelboard Instruction Leaflet E3A1071 RevG ...

Страница 2: ...tion SERVICE equipment 6 Chassis installation 6 Door in Door latch adjustment 6 CCPB branch disconnect installation removal 7 8 Branch circuit deadfront knockout removal 8 Fuse replacement 9 Typical wiring 10 Typical coordination panelboard schematics 11 Coordination panelboard replacement parts 12 13 CCPB branch disconnect and CUBEFuse replacement parts 14 Notes 15 ...

Страница 3: ...edence For the latest version of this Instruction Leaflet download Instruction Leaflet from the Eaton website at www Eaton com The contents of this Instruction Leaflet are not part of nor do they modify any prior or existing agreement commitment or relationship QUALIFIED PERSON For the purpose of this Instruction Leaflet a qualified person a is familiar with the subject equipment and the hazards i...

Страница 4: ... in minor or moderate injury NOTICE Indicates a hazardous situation which if not avoided could result in property damage Safety Concerns The following are important safety precautions that Powe R Line 3FQS Panelboard users should observe at all times This summary is not comprehensive It is assumed the user will follow standard safety precautions for working in an electrical environment For more in...

Страница 5: ... is bottom feed only NEMA 1 flush or surface mount enclosure NEMA 3R surface mount enclosure 1 Mount NEMA 1 box or NEMA 3R enclosure per ANSI NEMA PB 1 1 instructions NEMA 1 enclosure box can be rotated 180 to accommodate conduit feed 2 If installing NEMA 1 flush mount panelboard make allowances for finished wall thickness 3 Install Grounding Bar and Neutral Bar using supplied 10 32 x 1 2 long scr...

Страница 6: ...nd feed conductors as needed using appropriate hardware see NEMA PB 1 1 4 Check that all fasteners and wire terminals are tightened to specified torque values 5 Install deadfronts and trim as required 400A Neutral Bar 800A Neutral Bar 200A Neutral Bar Rotate chassis 180 for bottom feed DOOR IN DOOR LATCH ADJUSTMENT For NEMA 1 installations with the Door in Door front if the door trim latch does no...

Страница 7: ...w the installation steps below 1 De energize and lockout panelboard power supply 2 Remove branch circuit deadfront 2a Remove branch circuit knockout s from deadfront where CCPB is being installed 3 On the CCPB to be installed push the switch to the OFF O position and remove fuse if present 4 Align T slot on CCPB with branch sub assembly and slide CCPB into position until fully seated 5 Align hole ...

Страница 8: ... in all open branch circuit positions Loosen and remove 10 32 x 1 4 screw Slide CCPB out until T slot clears branch sub assembly and remove Branch circuit disconnects come factory installed with the appropriate branch circuit deadfront knockouts removed If installing additional CCPB branch disconnects follow these procedures 1 De energize and lockout panelboard power supply 2 Remove branch circuit...

Страница 9: ...ing Replace fuse only with one of equal rating If a replacement fuse with equal rating is not available order one from a Cooper Bussmann distributor If the distributor does not have a replacement in stock place an order for an emergency fuse shipment call 636 394 3877 between 8 00 A M and 4 30 p m Central Time or 314 995 1342 for after hours service 9 Insert replacement fuse until fully seated 10 ...

Страница 10: ...50A 175A 200A Main Feed Through Lugs Part numbers listed on pages 12 13 Use only 60 75 C Cu Al conductors 30 60A Compression 8AWG 1 0 30 60A Mechanical 2 14AWG 30 200A Double sub feed 300kcmil 6AWG 70 200A Compression 300kcmil 4AWG 70 200A Mechanical 300kcmil 6AWG 225 400A Compression 600kcmil 250kcmil 225 400A Mechanical 600kcmil 4AWG 225 400A Double sub feed 600kcmil 2AWG CCPB Ampacity Rejecting...

Страница 11: ...e 3 Wire GROUND Three Phase 3 Wire Main Lug Only Three Phase 3 Wire Fused Main Disconnect GROUND Three Phase 3 Wire Non Fused Main Disconnect GROUND NEUTRAL GROUND Three Phase 4 Wire Main Lug Only Three Phase 4 Wire Fused Main Disconnect NEUTRAL GROUND Three Phase 4 Wire Non Fused Main Disconnect NEUTRAL GROUND Single Phase 2 Wire Main Lug Only NEUTRAL GROUND Single Phase 2 Wire Fused Disconnect N...

Страница 12: ...pression lug 1 phase 3 wire 70 200A 2A1909 6 Kit mechanical lug 1 phase 3 wire 70 200A 2A1909 7 Kit double sub feed lug 1 phase 3 wire 30 200A 2A1909 8 Kit main disconnect 30 60A 1 phase 3 wire 2A1909 9 Kit main disconnect 30 60A 3 phase 2A1909 10 Kit compression lug 3 phase 30 60A 2A1909 11 Kit mechanical lug 3 phase 30 60A 2A1909 12 Kit compression lug 1 phase 3 wire 30 60A 2A1909 13 Kit mechani...

Страница 13: ...0 box E2A1667 11 Door in door surface for 69 box E2A1667 4 Door flush for 59 box E2A1667 12 Door in door flush for 69 box E2A1667 5 Door in door surface for 50 box E2A1667 17 Door surface for 50 box E2A1667 6 Door in door surface for 59 box E2A1667 18 Door flush for 50 box E2A1667 7 Door in door flush for 50 box E2A1667 19 Door in door surface for 50 box E2A1667 8 Door in door flush for 59 box E2A...

Страница 14: ...s R RN N T TC CF F a am mp ps s TCF1RN TCF3RN TCF6 CCPB of Poles 15CF TCF6RN TCF10RN TCF10 TCF15RN TCF15 CCPB of Poles 20CF TCF17 1 2RN TCF17 1 2 TCF20RN TCF20 CCPB of Poles 30CF TCF25RN TCF25 TCF30RN TCF30 CCPB of Poles 40CF TCF35RN TCF35 TCF40RN TCF40 CCPB of Poles 50CF TCF45RN TCF45 TCF50RN TCF50 CCPB of Poles 60CF TCF60RN TCF60 CCPB of Poles 70CF TCF70RN TCF70 CCPB of Poles 90CF TCF80RN TCF80 ...

Страница 15: ...E3A1071 RevG 15 NOTES ...

Страница 16: ...evG Eaton Corporation Electrical Sector 1111 Superior Ave Cleveland OH 44114 United States 877 ETN CARE Eaton com 2010 Eaton Corporation All Rights Reserved Printed in USA Publication No E3A1071 RevG December 2010 ...

Отзывы: