30
Washer
Rack mount rail
Wing Knob
1/4”-20 carriage bolt
Figure
21
Figure
9-
20
Guide slot
Rack mount
rail bracket
Figure
9-19
Network rail bracket
Spacer
1/4”-20 carriage bolt
RACK MOUNT RAILS
1. Loosely install ¼-20 carriage bolts, washers, and wing knobs into the rectangular mounting holes in the
rails. See figure
9-19
.
Longer rails typically have 3 mounting points; shorter rails have 2 mounting points.
Reducer style rails require 4” carriage bolts instead of the standard 1” bolts.
Rails that are to be installed into Network style enclosures require a stand-off spacer and a 4” bolt
at the center mounting position. See figure
9-21
.
All Rack Mount Rails have printed numbers next to the EIA hole pattern. Each number indicates
an industry standard “U” space
.
Orient the rails with the lower numbers towards the bottom.
Interior mounted divider panels should be installed before installing rack mount rails.
Frame mounted cable management kits should be installed before installing rack mount rails.
2. Engage the carriage bolt heads into the guide slots in the enclosure’s rail brackets. Slide the rails into po-
sition and then tighten the wing knobs.
Pub Num: MN159002EN rev1.0
Paramount Enclosure
Installation Guide