-NA, -CNA

(UL/CSA models)

NZM3(-4)-XKS

It is necessary to re-install

the barrier to maintain

proper electrical clearances!

XKC

a

XKS

Removal of XKC Pressure clamp connectors to re-install XKS Screw terminations.
Removal of XKC pressure clamp connector kits will enable re-installation

of XKS screw termination connectors.

Follow diagrams in this instruction sheet in reverse order to remove the XKC

pressure clamp connectors and proceed as shown above to re-install XKS screw terminations.

-NA, -CNA

(UL/CSA models)

It is necessary to re-install

the barrier to maintain

proper electrical clearances!

10

Z 2

1.2 Nm

(11 lb-in)

11

5 mm

19 Nm

(168 lb-in)

12

13a

push

ON

3

1

8 mm

31 Nm

(275 lb-in)

13b

13c

Z 2

1.2 Nm

(11 lb-in)

push