4 Configuring the device
4.2 MODBUS register
24
NZM-XMC Measuring and Communication Module
11/16 MN01219001Z-EN
www.eaton.com
Table 9: Electrical parameters
Para-
meter
no.
NZM…-XMC-…
NZM-XMC-TC-MB
Actual
value
register
Maximum
value
register
Minimum
value
register
R/W
Parameters
Unit
Parameters
Unit
high
low
high
low
high
low
1
Voltage L1
1 mV
Voltage L1
mV
0
1
96
97
192
193
R
2
Current L1
mA
Current L1
mA
2
3
98
99
194
195
R
3
Active power L1
W
Active power L1
W
4
5
100
101
196
197
R
4
Reactive power L1
var
Reactive power L1
var
6
7
102
103
198
199
R
5
Power factor L1
–
Power factor L1
–
8
9
104
105
200
201
R
6
Voltage L2
1 mV
Voltage L2
mV
10
11
106
107
202
203
R
7
Current L2
mA
Current L2
mA
12
13
108
109
204
205
R
8
Active power L2
W
Active power L2
W
14
15
110
111
206
207
R
9
Reactive power L2
var
Reactive power L2
var
16
17
112
113
208
209
R
10
Power factor L2
–
Power factor L2
–
18
19
114
115
210
211
R
11
Voltage L3
1 mV
Voltage L3
mV
20
21
116
117
212
213
R
12
Current L3
mA
Current L3
mA
22
23
118
119
214
215
R
13
Active power L3
W
Active power L3
W
24 V
25
120
121
216
217
R
14
Reactive power L3
var
Reactive power L3
var
26
27
122
123
218
219
R
15
Power factor L3
–
Power factor L3
–
28
29
124
125
220
221
R
16
Power 3-phase
W
Power 3-phase
W
30
31
126
127
222
223
R
17
Inductive reactive power
3-phase
var
Inductive reactive power
3-phase
var
32
33
128
129
224
225
R
18
Capacitive reactive power
3-phase
var
Capacitive reactive power
3-phase
var
34
35
130
131
226
227
R
19
Consumed capacitive
reactive energy L1
kvarh
3-phase cos
ϕ
–
36
37
132
133
228
229
R
20
Power factor 3-phase
–
Power factor 3-phase
–
38
39
134
135
230
231
R
21
Frequency cable Lx
Hz x 10
L1 frequency
Hz x 10
40
41
136
137
232
233
R
22
Consumed active energy L1
kWh
Voltage L1-L2
m V
42
43
138
139
234
235
R
23
Consumed
active energy L2
kWh
Voltage L2-L3
mV
44
45
140
141
236
237
R
24
Consumed
active energy L3
kWh
Voltage L3-L1
mV
46
47
142
143
238
239
R
25
Produced
active energy L1
kWh
% THD V1
% x 10
48
49
144
145
240
241
R
26
Produced
active energy L2
kWh
% THD V2
% x 10
50
51
146
147
242
243
R
27
Produced
active energy L3
kWh
% THD V3
% x 10
52
53
148
149
244
245
R