Step 4 — Parameter Groups & Default Values
Parameter Groups
The parameters are grouped according to the following descriptions:
10
Reserved (and not displayed)
20
Basic Grouping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
30
Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
40
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
50
Drive Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
60
Motor Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
70
Protective Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
80
Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
13
90
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
MVX9000 Parameter Listing
20 — BASIC GROUPING (Quick Start)
Modbus
Groups
Description
Range
Default
User
Settings
0000H
20.01
50.05
Motor Nameplate
Frequency
10.0 to 400.0 Hz
60.0
0001H
20.02
50.06
Motor Nameplate
Voltage
115/230V drives: 1.0 to 255V
230
460V drives: 1.0 to 510V
460
575V drives: 1.0 to 637V
575
0002H
20.03
50.01
Source of Master
Frequency
00: Master frequency determined by
digital keypad up/down
01
01: Master frequency determined by
keypad potentiometer
02: Master frequency determined by
0 to +10V input on AI terminal
03: Master frequency determined by
4 to 20 mA input on AI terminal
04: Master frequency determined by
RS-485 communication interface
0003H
20.04
50.02
Source of Operation
command
00: Operation commands
determined by digital keypad
00
01: Operation commands
determined by external control
terminals, keypad STOP is effective
02: Operation commands
determined by external control
terminals, keypad STOP is
ineffective
03: Operation commands
determined by RS-485 interface,
keypad STOP is effective
04: Operation commands
determined by RS-485 interface,
keypad STOP is ineffective
0004H
20.05
60.01
Motor Rated Current
30 to 120%
FLA
0005H
20.06
50.09
Minimum Output
Frequency
0.0 to 20.0 Hz
1.5
0006H
20.07
50.04
Maximum Output
Frequency
50.0 to 400.0 Hz
60.0
0007H
20.08
50.12
Acceleration Time 1
0.01 to 600.0 sec
10.0
0008H
20.09
50.13
Deceleration Time 1
0.01 to 600.0 sec
10.0