O&M Manual for 30-1000 Amperes

 Manual Transfer Switch

Section 4: Installation and Wiring

4.1 General

Transfer switches are factory wired and tested. Installation 

requires solidly mounting the enclosed unit and connecting power 

cables and auxiliary pilot circuits. Physical mounting procedures 

and power cable connections are covered in this section. Once a 

transfer switch is properly installed and wired, it should be 

mechanically and electrically checked for proper installation and 

operation. The procedures for these initial mechanical and electri-

cal checks are outlined in Section 6 of this instruction bulletin.

4.2 Mounting Location

Choose a location that offers a flat, rigid mounting surface capa-

ble of supporting the weight of the enclosed transfer switch 

equipment. Avoid locations that are moist, hot and/or dusty. 

Enclosure designs are, however, available for special environ-

ments. If there are any doubts as to location suitabil- ity, discuss 

it with your Eaton representative.

Check to make certain that there are no pipes, wires or other 

mounting hazards in the immediate mounting area that could cre-

ate a present or future problem.

Carefully remove all packing material from the transfer switch at 

the mounting location. Even though an equipment inspection was 

made when the equipment was received, make another careful 

inspection of the enclosure and the enclosed transfer switch as 

packing material is removed and the enclosure readied for mount-

ing. Be especially alert for distorted metal, loose wires or dam-

aged components.

4.3 Mounting Procedure

All transfer switch equipment enclosures are of the same design. 

Only the overall physical dimensions change. The enclosure is 

provided with four elongated mounting holes, two in the top 

mounting flange and two in the bottom.

If the transfer switch equipment is of the vertical design, the 

power panel is provided with two sets of mounting holes. One 

set positions the panel for top entry of cables and one set for bot-

tom entry (Figure 13). This will be covered in more detail later in 

Section 4.4 Vertical Design Load Lug Location.

Transfer switch equipment is assembled and supplied as standard 

for top entry, although equally adaptable to bottom entry. Cable 

entry holes are not part of the enclosure when shipped from the 

factory and must be provided in the field, either before or after 

mounting the enclosure.

  

NOTICE

TO FACILITATE THE PROCEDURES DESCRIBED IN THIS SECTION, 

THE SOLID STEEL SHIELD OVER THE POWER PANEL SHOULD BE 

REMOVED.  THE SHIELD IS ATTACHED TO THE RATCHET ASSEM-

BLY WITH FOUR SCREWS.  REMOVE THE FOUR SCREWS AND 

SHIELD UNTIL THE PROCEDURES ARE COMPLETED.

    

 

WARNING

BE CERTAIN THAT THE SOLID STEEL POWER PANEL SHIELD IS 

PROPERLY INSTALLED BEFORE THE TRANSFER SWITCH EQUIP-

MENT IS PUT INTO SERVICE.  THE SHIELD PROVIDES PROTECTION 

FROM DANGEROUS VOLTAGES AT THE LINE AND LOAD TERMI-

NALS WHEN THE EQUIPMENT IS IN OPERATION.  FAILURE TO DO 

SO COULD RESULT IN PERSONAL INJURY OR DEATH.

    

CAUTION

SINCE THE ENCLOSED ATS MUST BE LIFTED INTO PLACE FOR 

MOUNTING, BE CERTAIN THAT ADEQUATE RESOURCES ARE 

AVAILABLE FOR LIFTING TO AVOID PERSONNEL INJURIES OR 

EQUIPMENT DAMAGE.

    

CAUTION

EXTREME CARE SHOULD BE TAKEN TO PROTECT THE TRANSFER 

SWITCH FROM DRILL CHIPS, FILINGS, AND OTHER CONTAMI-

NANTS WHEN MAKING THE CABLE ENTRY HOLES.  EXTREME CARE 

SHOULD ALSO BE TAKEN WHEN MOUNTING THE ENCLOSURE TO 

PREVENT COMPONENT DAMAGE OR A FUTURE MALFUNCTION.

Содержание MTVXKDA20225WRU

Страница 1: ...m O M Manual for 30 1000 Amperes Manual Transfer Switch Instruction Booklet Description Page Introduction 2 Receiving Handling and Storage 5 Equipment Description 6 Installation and Wiring 10 Operatio...

Страница 2: ...eding If further information is required by the purchaser regard ing a particular installation application or maintenance activity an Eaton representative should be contacted 1 1 1 Warranty and Liabil...

Страница 3: ...rugged compact design utilizing molded case switches to effect the transfer of essential loads from one power source to another Figures 3 4 and 5 Molded case switches are interlocked to prevent both s...

Страница 4: ...00 Amperes Manual Transfer Switch Table 2 Transfer Switch Catalog Number Explanation Figure 3 Vertical Design Automatic Transfer Switch Equipment with Deadfront Cover in Place Over Power Panel 225 100...

Страница 5: ...affixed to the top of the shipping container which includes a variety of equipment and customer information such as General Order Number GO and Catalog Number Cat Make certain that this information ma...

Страница 6: ...stance stack other equipment on top of a transfer switch equipment enclosure whether packaged or not Section 3 Equipment Description 3 1 General Eaton transfer switch equipment is available in four d...

Страница 7: ...The switches incorporate pos itive quick make quick break toggle mechanisms and DE IONT arc chutes Vertically mounted switching devices are mechanically and electri cally interlocked to prevent the t...

Страница 8: ...Both N E Selectable or Load line 2 DP 4000 Normal or Emergency or Both N E Selectable or Load line 3 Custom metering available contact Eaton 20A Rear Bus Connections Front connected solder less lugs...

Страница 9: ...e and or C In legally required standby systems in accordance with article 701 of the National Electrical Code Since Eaton Transfer Switches utilize specially designed molded case switches and or molde...

Страница 10: ...ting Procedure All transfer switch equipment enclosures are of the same design Only the overall physical dimensions change The enclosure is provided with four elongated mounting holes two in the top m...

Страница 11: ...and set aside in a safe place until mounting is complete Step 2 Install required mounting bolt anchors and the two upper mounting bolts in the mounting surface Step 3 Gently lift the enclosure and gu...

Страница 12: ...removed Figure 8 Step 5 The load lug assembly just mentioned is removed by first removing the six or eight bolts securing the pieces of insulated bus to the back of the power panel The num ber of mou...

Страница 13: ...glass polyester phase barriers are in place and positioned properly in the grooves provided When making any bolted connection to the bus comply with the torque requirements as outlined in Table 4 Tab...

Страница 14: ...holes in the power panel with the pre tapped inserts in the rear of the enclosure Step 10 With the power panel held securely against the back of the enclosure replace and tighten the four mounting bol...

Страница 15: ...Step 6 Tighten cable lugs to the torque identified on the label affixed to the unit immediately adjacent to the lugs Step 7 Make necessary connections of options using wiring dia grams and Quick Start...

Страница 16: ...600 Vac are provided Figure 9 A small disconnect plug is provided to change from one voltage to another Horizontal Design Voltage Selection Horizontal design transfer switches are furnished with an ad...

Страница 17: ...of the handle to open and or close the main contacts Figure 19 The three switch positions Normal Neutral and Emergency are visually indicated on the indi cator wheel Figure 20 To manually operate the...

Страница 18: ...individual representing company 6 Basic description of the situation as it exists 7 Any results of the problem solving steps taken and or read ings taken 6 2 1 Transfer Switch Appears In inoperative S...

Страница 19: ...rol power is switched off by disconnecting all logic plugs b Inspect structure area for safety hazards or potential maintenance problems Inspect area especially where molded case switching devices are...

Страница 20: ...N RECOMMENDATIONS AND DESCRIPTIONS CON TAINED HEREIN In no event will Eaton be responsible to the pur chaser or user in contract in tort including negligence strict liability or otherwise for any spec...

Отзывы: