INM831B Rev 4 

 

 

Base of unit 

Rail mounting position 

Tooth 

Retaining arm 

Base moulding 

Mounting clip 

Surface mounting position 

Figure 2

 - Adjusting base clips for rail or surface-mounting 

3.2.2

 

Mounting on a flat surface (figures 2 and 3)

 

Turn the unit upside down. 
With  a  screwdriver,  apply  an  anti-clockwise  force  against  the 

retaining arm of one of the base clips to release it from its  recess. 
Hold the arm in this position and slide the clip outwards. 
Release the retaining arm to engage the tooth in the base moulding. 
Adjust the position of the other two clips with a similar procedure. 
Mount on any flat surface using three M4 bolts or screws (or other 

suitable fasteners with a shank diameter of 4mm or less) through the 

three clips according to the mounting centres shown in figure 3. 

 

3.2.3

 

Mounting in an ENC8, ENC8-SS, ENC83 or 

ENC83-SS enclosure (figure 4) 

Remove  the  upper  and/or  lower  undrilled  gland  plates  and  drill 

suitable  holes  for  the  entry  glands  required.  Possible  hole 

configurations are listed in the table. 
Mount  the  unit  on  the  internal  T-section  rail  of  the  enclosure  as 

described in (1). 
Mount the enclosure on any flat surface using four M8 bolts (or other 

suitable fasteners with a shank diameter of 8mm or less) through the 

four fixed lugs according to the mounting centres shown in figure 4. 

Table 1  Recommended gland entries

 

 

Mounting 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 

Removal 

 
 
 

 

Twist screwdriver 

to release clip 

 

 

Side of unit 

 
 
 
 
 
 
 
 
 

Centre mounting clip 

 

Figure 1

 - Rail-mounting and removal 

 

 

 

 

 

 
 

 

80 

 

 

 

 

 

 

 

130 

 

Figure 3

 - Mounting centres, surface mounting 

Intrinsically 

Safe System 

TAKE CARE 

x i

010

C   D 

010

155

160

Figure 4

 - Enclosures and their dimensions 

 

A

 

B

 

C

 

D

 

ENC8

 

331

 

306

 

203

 

306

 

ENC83

 

407

 

380

 

305

 

466

 

 

Entry size 

(mm)

 

Recommended 

maximum no. 

of entries

 

Minimum distance 

between centres 

(mm)

 

16

 

13

 

40

 

20

 

9

 

45

 

25

 

6

 

50

 

32

 

4

 

64

 

40

 

3

 

80

 

Содержание MTL831B

Страница 1: ......

Страница 2: ...ECTIONS 3 4 1 RTD inputs 3 4 2 THCs and mV inputs 5 4 3 Mixed inputs 5 4 4 Highway connections 5 4 5 MTL3052 digital isolator 6 4 6 Multi transmitter connections 6 4 7 Cable screens 7 5 Configuration 7 5 1 Transmitter Address 7 5 2 RTD mode setting 7 6 ATEX information 8 6 1 General 8 6 2 Installation 8 6 3 Inspection and maintenance 8 6 4 Repair 8 6 5 Marking 8 6 6 Specific Conditions of Use 8 ...

Страница 3: ... highway connections If units are installed in our enclosures it details any special wiring arrangements Configuration the address and input mode selection by the setting of internal switches Note A new user might find it helpful to set up the system or a simple version of it in an indoor test area to gain familiarisation before undertaking installation on site 3 MECHANICAL INSTALLATION 3 1 Locati...

Страница 4: ...ting in an ENC8 ENC8 SS ENC83 or ENC83 SS enclosure figure 4 Remove the upper and or lower undrilled gland plates and drill suitable holes for the entry glands required Possible hole configurations are listed in the table Mount the unit on the internal T section rail of the enclosure as described in 1 Mount the enclosure on any flat surface using four M8 bolts or other suitable fasteners with a sh...

Страница 5: ...tation current connect terminal 39 to 41 and connect terminal 40 to 42 The unit can then calculate the current from the voltage developed across the built in 100 ohm resistor 2 wire RTD increased measurement accuracy Lead resistance in 2 wire applications causes inaccuracy Accuracy can be increased by substituting the wire link step 2 above with a resistor equal in value to the resistance of the l...

Страница 6: ...ad of each RTD except the last and the ve source lead of the next RTD 5 Connect the ve source lead of the first RTD to the ve end of the current loop terminal 7 6 Connect the ve source lead of the last RTD to the ve end of the current loop terminal 38 7 To monitor the RTD excitation current connect terminal 39 to 41 and connect terminal 40 to 42 The unit can then calculate the current from the vol...

Страница 7: ...d that they all are and will remain effectively at the same earth potential 4 3 Mixed inputs The ability to mix different input sensor types depends on the configurations available with the MTL838B receiver selected See the instructions supplied wtih the MTL838B receiver for details Connect the different sensors appropriately as described in sections 4 1 and 4 2 above 4 4 Highway connections The d...

Страница 8: ...ne or two data highways between output terminal pairs H1 terminals 1 and 2 and or H2 terminals 4 and 5 to the equivalent terminals on a second MTL831B transmitter terminals 3 and 4 for H1and terminals 1 and 2 for H2 NB two MTL831B transmitters or one MTL831B plus one MTL831 or two MTL832 transmitters can be linked in this way Hazardous area Safe area Serial data link to host computer mV THCs RTDs ...

Страница 9: ... can be removed Replacement of the blue terminal strip is the reverse of its removal instructions 5 1 Transmitter Address Four addresses 1 to 4 are possible with the SW100 switch settings as shown in Figure 13 Transmitter addresses must start at address 1 and must be sequential This means that two transmitters must have addresses 1 and 2 not 1 and 3 or 1 and 4 If only one transmitter is connected ...

Страница 10: ...cessive dust moisture and other contaminants 6 2 1 MTL831B This is IS apparatus and is normally mounted in a hazardous area It meets the requirement of Category 1 apparatus and may be installed in a Zone 0 or a Zone 1 location provided that the relevant installation requirements are met 6 2 2 MTL3052 This is associated apparatus and is always mounted in a safe area 6 3 Inspection and maintenance a...

Страница 11: ...INM831B Rev 4 9 ...

Страница 12: ......

Отзывы: