APPENDIX B - ALARM EVENT LOG

The multiplexer maintains a log of alarm events that may read using the Instrument 
Management Software. The types of event that might appear can be grouped into the 
following categories:

• 

General information

• 

Multiplexer internal parameters or values

• 

Diagnostic errors causing reset

The possible event log messages are listed below by category, and the meaning or 
appropriate action is supplied beside them.

General logs

Meaning or required action

!Alarm generated by HART test command 242

MTL diagnostic test activated

!No storage space for transmitter

Memory full of field device data

!Found a pre Rev 5 HART transmitter

Check manufacturer for update

!Other master detected on loop

Secondary master present

!Alarm Clear input used to reset alarms

Download of bootloader started

Firmware update in progress

Bootloader download complete, module will restart

Firmware update completed

Debug mode. No CRC installed in flash memory

Reset due to Watchdog or Brownout

See list of causes below

Module Powered Up

Module failed watchdog test

Return to MTL if alarm persists.

Warm start - Event Log or status corrupt

Unknown reason for module reset

Logs followed by a value:

Meaning or required action

!Duplicate Transmitter Unique Id. ID used on loop

Check manufacturer for update

!+12V Supply out of range

Check power supply to multiplexer is 
within specification.  
Return to MTL if alarm persists.

!-12V Supply out of range

Return to MTL if alarm persists.

!VBias out of range

Return to MTL if alarm persists.

!VLeak out of range

Return to MTL if alarm persists.

Power up scan complete - Transmitters found = 

Number, 0-32

Logs followed by 2 values:

Meaning or required action

!VH signal out of range

Check power supply to multiplexer is 
within specification.  
Return to MTL if alarm persists.

 

Log messages following an error that caused 
the module to reset

Meaning or required action

!CRC error in RAM copy of serial number

Return to MTL if alarm persists.

!CRC error in RAM image of configuration parameters

Return to MTL if alarm persists.

!An internal watchdog reset occured

Return to MTL if alarm persists.

!A clock monitor reset occured

Return to MTL if alarm persists.

!Module restarted due to failure in Startup Ram test

Return to MTL if alarm persists.

!Background RAM word test failed

Return to MTL if alarm persists.

!Background Ram byte test failed

Return to MTL if alarm persists.

!Background Ram block test failed

Return to MTL if alarm persists.

!Cold start flash test failed

Return to MTL if alarm persists.

!Incremental flash test failed

Return to MTL if alarm persists.

!Incremental flash test switch variable corrupt

Return to MTL if alarm persists.

!Illegal instruction trap did not execute 

Return to MTL if alarm persists.

!Stack overflowed

Return to MTL if alarm persists.

!Stack underflowed

Return to MTL if alarm persists.

Содержание MTL4850

Страница 1: ...DRAFT 11 December 2014 MTL4850 and MTL4854 HART Connection Systems March 2015 INM 4850_54 Rev4 Instruction Manual MTL HART Interfacing Solutions...

Страница 2: ...lier harmonised standards a subsequent review has determined that technical knowledge is unaffected by the current harmonised standards listed above Product Description EMC1 LVD2 ATEX3 Cat1 Cat2 ATEX...

Страница 3: ...ng Read and understand the contents of this manual and the product datasheet Ensure installation and operating personnel have received adequate training for this task Ensure that any operating instruc...

Страница 4: ...iv DRAFT 11 December 2014 INM MTL4850_54 Rev4 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 5: ...ation and tagging 17 4 9 Backplane earth rails 17 4 10 Backplanes connections 18 4 11 Cabling recommendations 20 4 12 RS485 connection 20 5 MODULES 22 5 1 MTL4850 installation 22 5 2 Isolator modules...

Страница 6: ...vi DRAFT 11 December 2014 INM MTL4850_54 Rev4 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 7: ...pecifications of the MTL4850 system components and accessories and the MTL4500 Series isolators mentioned in this manual 2 DESCRIPTION The MTL4850 HART Maintenance System enables a user to calibrate c...

Страница 8: ...ideration must be given to the safety parameters for each field loop For further information please refer to MTL or your local representative The MTL4850 has a single HART modem to service the channel...

Страница 9: ...vice wiring These are not designed for any particular DCS type and may be used universally The alternative is to choose a connection unit or backplane that integrates with the type of DCS being used o...

Страница 10: ...ions 4 2 to 4 5 for details The final method considered here consists of two backplane options 16 channel backplane CPH SC16 and CPH SC16R 32 channel backplane CPH SC32 and CPH SC32R Both backplanes a...

Страница 11: ...ing to and from the field devices the HTP SC32 will often be the primary method of choice It is intended for analogue input signals but may also be used for analogue outputs if the host system is comp...

Страница 12: ...put DCS input 24V or Tx from DCS Tx 2 wire transmitter input A B Tx Ch HART Tx Ch 200 50 Figure 4 2b HTP SC32 S200 for 2 wireTx DCS input DCS input Tx 4 wire transmitter input A B HART Ch 250 Link Ch...

Страница 13: ...s shown in Figure 4 3 4 1 5 HART addressing A 6 way DIP switch SW1 is provided on the circuit board to enable a unique HART address to be set for the HART multiplexer The switch is binary coded and th...

Страница 14: ...software and to onward link to other HMP HM64 or similar HART interfaces Full details of this communications link are provided in Sections 4 12 4 2 4 DC power connections The HMP HM64 has a removable...

Страница 15: ...eater mechanical protection However this is normally unnecessary as to maintain integrity each group of cabinets would communicate their HART signals via independent MTL4850 54 modules using the RS485...

Страница 16: ...circuit board to fit parallel resistors normally 250W or an appropriate series resistor to raise the impedance if it is 240W This unit can be used with analogue outputs if the system s current signal...

Страница 17: ...DRAFT 11 December 2014 DRAFT 11 December 2014 INM MTL4850_54 Rev4 11 HMP HM64 HART INTERFACE Figure 4 7 HCU16 schematic diagram...

Страница 18: ...with a low pass filter in series with the current signal from the system This has virtually no effect on the 4 20mA signals but presents a suitable high impedance 240W to the HART signals for their d...

Страница 19: ...DRAFT 11 December 2014 DRAFT 11 December 2014 INM MTL4850_54 Rev4 13 HMP HM64 HART INTERFACE Figure 4 9 HCU16AO schematic diagram...

Страница 20: ...linked in this way only one will have the multiplexer modules fitted The MTL4850 54 is fitted to the backplane that carries modules 1 16 the RS485 serial link should also be connected to this backplan...

Страница 21: ...DRAFT 11 December 2014 DRAFT 11 December 2014 INM MTL4850_54 Rev4 15 Figure 4 10 CPH SC16 R backplane Figure 4 11 CPH SC32 R backplane Carrier weight 415g nominal Carrier weight 420g nominal...

Страница 22: ...her B and a plain washer C over it c Insert the screw through a fixing hole on the baseplate d Fit a 10mm spacer D and retain it with washer E e Repeat steps a to d for the other five 5 mounting holes...

Страница 23: ...ngstripmountingpost 1 withtwoM3x12 mountingscrews 2 andwashers 3 c Attach colour coding labels 6 onto tag label 5 d Mark tag label 5 with tag references e Slide tag label 5 into tag strip holder 4 and...

Страница 24: ...channel terminals are used for input or output field devices because the backplane provides the required interconnections Maximum wire gauge is 2 5mm2 12 AWG and the wire enters from the side of the...

Страница 25: ...e without affecting supplies to other backplanes Two or more backplanes can be removed provided they are neighbours without disrupting the supply to other backplanes Make the connections as shown in F...

Страница 26: ...S232 or USB for serial communication however this interface type does not allow the communications network to extend beyond 10 to 20 metres in length MTL have chosen to use an RS485 serial interface w...

Страница 27: ...ng it is suggested that the same colour convention is used for all connections to backplane terminals A and B e g red to A black to B NOTE No damage will occur if the signalling lines are connected wi...

Страница 28: ...ress switches are binary coded and the address is set by constructing the required number from the switch options provided i e 1 2 4 8 16 and 32 For example address number 29 would be set by putting s...

Страница 29: ...s occurred 2 Check that backplane power LEDs are ON If not check the power supply fuse s and if necessary change any of them 3 Check that the PWR power LED on the MTL4850 54 module is ON If not and th...

Страница 30: ...y undertake the tests and routine maintenance described in sections 6 2 and 6 3 If an MTL4500 module is judged faulty repairs or modifications MUST NOT be made as these may affect the intrinsic safety...

Страница 31: ...system to pass HART data to any IMS that utilises the FDT DTM concept The DD and DTM files are free of charge and can be downloaded from the MTL website at www mtl inst com product hart_software 7 3...

Страница 32: ...with the appropriate European national and local regulations which may include reference to the code of practice IEC EN 60079 14 In addition particular industries or end users may have specific requir...

Страница 33: ...the Declaration of Conformity on page ii these products are included in the ATEX Cat3 certificate number MTL08ATEX4850X 9 APPENDIX A TYPICAL COMPATIBLE SYSTEMS MTL offer a range of backplanes for mou...

Страница 34: ...update 12V Supply out of range Check power supply to multiplexer is within specification Return to MTL if alarm persists 12V Supply out of range Return to MTL if alarm persists VBias out of range Retu...

Страница 35: ...MTL if alarm persists Sequence error Main initialisation Return to MTL if alarm persists Sequence error Main startup Return to MTL if alarm persists Sequence error First Field I O Return to MTL if ala...

Страница 36: ...22 73 98 12 0 Fax 49 0 22 73 98 12 2 00 E mail mtlgmbh eaton com INDIA MTL India No 36 Nehru Street Off Old Mahabalipuram Road Sholinganallur Chennai 600 119 India Tel 91 0 44 24501660 24501857 Fax 91...

Отзывы: