Control Circuit Devices M22-
SWD…
70
06/09 AWB2723-1613en
Commissioning
The automatic addressing of all slaves in the SmartWire-
Darwin network is performed via the gateway (actuation of
the configuration pushbutton on the gateway) during
commissioning. During the addressing process the
SmartWire Darwin diagnosis LED on the rear side of the
M22-SWD front function element flashes. Once the
addressing process is completed, the LED indicates a green
continuous light.
Exchange of Modules
After replacement of the modules and connection of the
voltage the configuration button must be pressed. The new
module is assigned an address by this means.
h
Caution!
Replacement of the SmartWire-Darwin function elements
is not permitted until the entire SmartWire-Darwin system
has been switched off.
h
Caution!
The sequence of the SmartWire-Darwin slaves must not be
altered.