NPServe Users Guide 

Users GUide

   MN024002EN   February 2017

6.  DNP is a very extensive protocol with multiple 

conformance levels and various data representations. 

Inconsistencies between what a SCADA Master 

expects and what a virtual DNP profile specifies lead to 

puzzling results in the control room. SCADA Masters 

are complex software themselves and getting access to 

the raw data may be incongruous. Raw traffic capture 

data is critical for Eaton engineers when diagnosing 

these issues.

Virtual settings

1.  Upload Profile – Select a file provided by Eaton to 

configure the NPServe DNP Virtual configuration.

2.  Profile – Select which uploaded profile to use.
3.  Slave Address – Set the DNP Slave address of the 

NPServe.

4.  Master Address – Set the expected DNP Master 

address.

5.  Submit Changes – Apply changes in this tab to the 

NPServe Configuration.

Possible troubleshooting

1.  Ensure that the NPServe has a valid SCADA 

configuration.

2.  Ensure that Communications settings are set up 

correctly.

3.  If bytes are received, then Master is not reaching the 

NPServe.

4.  If bytes are received but not transmitted, NPServe is 

rejecting requests from the Master, possibly due to 

mismatched DNP addresses.

5.  Traffic capture can provide insights into some issues; 

please initiate to find more low level information.

Diagnostics

1.  Download a diagnostic file to submit to Eaton for 

further troubleshooting.

2.  Display INCOM Comm Statistics:

Displays low-level INCOM communications statistics. 

Most counters are intended for Eaton troubleshooting 

but the following are end user interpretable:

BCH Errors – Counts the number of corrupted data 

messages due to bad wiring, mismatched addresses or 

other INCOM issues

The second table is a per device statistics table. 

Non-zero values for any statistic indicate possible 

problems with the specific device or wiring.

System

This page is used to verify the firmware version and to 

upload necessary firmware updates as necessary.

otee:

N

NPServe can be reset to factory default status if 

desired. It is recommend to save the configuration 

before resetting.

USB maintenance port

The USB Maintenance port provides access to a graphical 

maintenance web page via a USB-to-Ethernet connection.

Required components

Ethernet Cable

Recommended connector – Plugable USB 2.0 OTG 

Micro-B to 10/100 Fast Ethernet Adapter for Windows 

Tablets & Raspberry Pi Zero (ASIX AX88772A chipset)

Host PC or Laptop

Accessing the maintenance web page

1.  If using a laptop, disable the wireless Ethernet 

functionality.

2.  Connect one end of the Ethernet cable to the plugable 

adapter.

3.  Connect the other end of the Ethernet cable to the host 

PC.

4.  Plug the MicroUSB end of the adapter into the 

NPServe MicroUSB port.

5.  Open a web browser and go to the following URL: 

http://eaton.console.

You should now be at the maintenance page.

Troubleshooting the access procedure

1.  Make sure the wireless is disabled.
2.  Try to browse to http://10.42.83.1 instead of http://

eaton.console.

3.  Make sure your IP address is similar to 10.42.83.100 

(last number can vary).

4.  Try rebooting the Host PC.

Содержание MN024002EN

Страница 1: ...NPServe Users Guide Comm Module MN024002EN Effective February 2017 ...

Страница 2: ...SE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability or otherwise for any...

Страница 3: ...ER OF WARRANTIES AND LIMITATION OF LIABILITY ii SAFETY FOR LIFE iv SAFETY INFORMATION iv Safety instructions iv NPSERVE USERS GUIDE 1 Connections 1 Connection details 2 Real time data 3 Configuration 3 DNP SCADA 4 Diagnostics 5 System 5 USB maintenance port 5 ...

Страница 4: ...ll result in death or serious injury WARNING Indicates a potentially hazardous situation which if not avoided could result in death or serious injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in minor or moderate injury CAUTION Indicates a potentially hazardous situation which if not avoided may result in equipment damage only Safety instructions Following...

Страница 5: ...accessed This guide is intended solely to provide user guidelines on the features connections and possible troubleshooting points of the NPServe device Connections The NPServe has the following connections Relay 1 30A INCOM Ethernet Micro USB DNP Port 2 DNP Port 1 Analog Inputs Analog PS MPCV Pendant Digital Inputs Power Relay 2 10A Relay 3 10A Note N Each connection can be selected via the Home w...

Страница 6: ...e the icon is selected verify the INCOM compatible device is connected 1 Verify that INCOM wiring is carried out per IL TD17513 2 Verify the INCOM device is powered and active 3 Verify that NPServe has auto learned devices connected to it or has INCOM devices in the configuration uploaded Ethernet connection The Ethernet connection is for the network LAN connections The port can be used to connect...

Страница 7: ...state before connection 3 Verify the Status change of the device via the Web Home page Digitial Input display see Figure 6 4 Ensure that there are 0 V between RET and AC Neutral 5 Ensure there are 120 V across an open connection Real time data Once various INCOM and DNP devices are connected all of the various data will be displayed under the Real Time Data link at the bottom of the web Home Page ...

Страница 8: ...ot be changed by control 3 Press the Commit button to save the relay states to NPServe DNP SCADA Status Link Type How NPServe hooks up to DNP Master may be UDP or RS 485 Link Status Whether NPServe is responding to DNP requests Bytes Transmitted How many bytes NPServe has sent to Master since bootup or communications reconfiguration Bytes Received How many bytes NPServe has received since bootup o...

Страница 9: ... level INCOM communications statistics Most counters are intended for Eaton troubleshooting but the following are end user interpretable BCH Errors Counts the number of corrupted data messages due to bad wiring mismatched addresses or other INCOM issues The second table is a per device statistics table Non zero values for any statistic indicate possible problems with the specific device or wiring ...

Страница 10: ...te the Maintenance IP Configuration fields as per your network specification 2 Click Commit and the present setting will update to reflect your input Test mode Test mode turns off the normal functionality of the NPServe and gives access to low level functions Reboot Reboots the NPServe Reset to Factory Defaults Clearing the configuration from this page will do a low level format of the data storag...

Страница 11: ...7 NPServe Users Guide Users Guide MN024002EN February 2017 This page is intentionally left blank T ...

Страница 12: ...States Eaton com 2017 Eaton All Rights Reserved Printed in USA Publication No MN024002EN February 2017 Eaton is a registered trademark All trademarks are property of their respective owners SAFETY FOR LIFE For Eaton product information visit www eaton com ...

Отзывы: