Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117—Rev 01
1
C
Chhaapptteerr 11 IInnttrroodduuccttiioonn
11..11
IInntteennddeedd U
Ussee
The 30 kVA Mini PDU can be placed next to server racks, providing local power distribution. The unit has
casters and is easily repositioned. All input and output power connections are plug-in and no wiring to circuit
breakers or lugs is required on site.
Figure 1. Mini PDU
Cable Ladder
Server Racks
30 kVA Mini PDU
11..22
D
Deessccrriippttiioonn
Table 1. Dimensions and Weight
Dimensions
48"H x 16"W x 42"D
Casters and Leveling feet
add 0-1.5"H
Weight
Approx. 850 lbs.
Table 2. Circuit Breakers
Specification
Quantity
Main circuit breakers (CBs)
150AF thermal magnetic, actual trip=45AT, 100% rated,
kAIC@480 VAC=35
1
150AF, thermal magnetic, actual trip=80A, 100% rated,
kAIC@208VAC=65
1
Output Branch Circuit Breakers
42-pole, 3-phase, 225A, standard NQM panelboard
1
30A, 2-pole, 208VAC, 10 kAIC
16
20A, 1-pole, 120VAC, 10 kAIC
4
Certified by UL/CSA
Certification standard: UL 62368
11..33
EEnnvviirroonnm
meennttaall S
Sppeecciiffiiccaattiioonnss
•
Ambient operating temperature range: 0
⁰
C to: 45°C
Содержание Mini PDU
Страница 1: ...p n 164001117 Revision 01 Installation and Operation Manual Eaton 30 kVA Mini Power Distribution Unit...
Страница 8: ......
Страница 16: ...4 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Introduction...
Страница 18: ...6 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Safety...
Страница 26: ...14 Eaton 30 kVA Mini Power Distribution Unit Installation and Operation Manual 164001117 Rev 01 Power Cabling...
Страница 36: ...16400111701 164001117 01...