Installation
04/10 MN04020001Z-EN
44
Function of the control signal terminals
The functions that are set in the ex-factory and the electrical
connection data of all control signal terminals are listed in the
following table.
Table 4:
Factory-set functions of the control terminals
Terminal
Signal
Factory setting
Description
1
+10V
Output nominal voltage
-
Maximum load 10 mA, reference potential GND
2
AI1
Analog signal input 1
Frequency reference value
1)
0 - +10 V (R
i
> 200 k
O
)
0/4 - 20 mA (R
B
= 200
O
)
Selectable through microswitch S2
3
GND
Reference potential
-
0 V
4
AI2
Analog input 2
PID controller, actual value
1)
0 - +10 V (R
i
> 200 k
O
)
0/4 - 20 mA (R
B
= 200
O
)
Selectable through microswitch S3
5
GND
Reference potential
-
0 V
6
24V
Control voltage for DI1 - DI6,
output (+24 V)
-
Maximum load 50 mA, reference potential GND
7
DI-C
Reference potential of the
digital inputs DI1 - DI6
LOGIC- (GND)
Selectable through microswitch LOGIC –/+
8
DI1
Digital input 1
FWD start enable, forward
1)
0 - +30 V (R
i
> 12 k
O
)
9
DI2
Digital input 2
REV start enable, reverse
1)
0 - +30 V (R
i
> 12 k
O
)
10
DI3
Digital input 3
Fixed frequency
B0
1)
0 - +30 V (R
i
> 12 k
O
)
13
DO-
Digital output
Active = READY
1)
Transistor, max. 50 mA, supply voltage control
signal terminal 20
14
DI4
Digital input 4
Fixed frequency B1
1)
0 - +30 V (R
i
= 12 k
O
)
15
DI5
Digital input 5
Error acknowledgment
1)
0 - +30 V (R
i
= 12 k
O
)
16
DI6
Digital input 6
PI controller deactivated
1)
0 - +30 V (R
i
= 12 k
O
)
18
AO
Analog output
Output frequency
1)
0 - +10 V, max. 10 mA
20
DO+
Digital output
Supply voltage, see control
signal terminal 13
Supply voltage for digital output DO max.
48 V DC, max. 50 mA
22
R13
Relay 1, normally open contact
Active = RUN
1)
Maximum switching load:
250 V AC/2 A or 250 V DC/0.4 A
23
R14
Relay 1, normally open contact
Active = RUN
1)
Maximum switching load:
250 V AC/2 A or 250 V DC/0.4 A
24
R22
Relay 2, changeover contact
(N/C)
Active = FAULT
1)
Maximum switching load:
250 V AC/2 A or 250 V DC/0.4 A
25
R21
Relay 2, changeover contact
Active = FAULT
1)
Maximum switching load:
250 V AC/2 A or 250 V DC/0.4 A
26
R24
Relay 2, changeover contact
(N/O)
Active = FAULT
1)
Maximum switching load:
250 V AC/2 A or 250 V DC/0.4 A
A
A
RS485 signal A
BUS-Communication
Modbus RTU
B
B
RS485 signal B
BUS-Communication
Modbus RTU
1) Programmable function (
Содержание M-Max series
Страница 8: ...04 10 MN04020001Z EN 4...
Страница 12: ...04 10 MN04020001Z EN 8...
Страница 58: ...04 10 MN04020001Z EN 54...
Страница 66: ...04 10 MN04020001Z EN 62...
Страница 138: ...04 10 MN04020001Z EN 134...
Страница 150: ...04 10 MN04020001Z EN 146...
Страница 196: ...04 10 MN04020001Z EN 192...