3
Instructional Booklet
IB02601010E
Effective October 2013
IQ35M-ENC enclosure
installation guide
eaton
www.eaton.com
Step 2. Mount the IQ35M-ENC enclosure to a wall or a panel
Cut holes in the enclosure for wire conduit connections prior to the
installation of the meter in the enclosure. After running the wiring,
seal all holes properly to maintain the enclosure rating. If using
metallic conduit, bonding between the conduit connections is not
automatic and must be provided as a part of the installation.
Take care to protect the equipment from drill chips, filings, and other
contaminants when making the wire entry holes and mounting the
enclosure to prevent component damage or a future malfunction.
Use the included mounting hardware to attach the mounting feet
to the enclosure. Then mount the enclosure to the wall or the
panel using either a 4-point or 2-point configuration (hardware for
mounting to the wall/panel is provided by the installer). The 4-point
configuration is shown below. For a 2-point configuration, mount the
feet as shown, but rotate the bottom feet 180 degrees so that they
are flush against the back of the enclosure.
Step 3. Install IQ 35M Series meter onto DIN rail
inside the IQ35M-ENC
Run meter wiring through the holes drilled previously. Wire the
meter according to the instructions in the meter installation guide.
Push the top of the meter onto the DIN rail.
Push the bottom of the meter onto the DIN rail until there is an
audible click.
Lower the four brackets so that the swing panel cover can be
attached using the enclosed hardware.