Eaton - Lighting Systems                                                    iLight Product Series - UIG-2    73-898-00     IM8840     Iss.02               4

Outputs

4 LED Outputs

A. LED outputs drive remote indicators

B. Each output provides a 10mA supply 

capable of driving LED’s up to a forward drop 

of 6.7V.

C. Indicates input status when opto-isolated 

input are configured for scene selection

D. Can also be configured for indication of 

other functions

E. All LED outputs wire with 2 part connectors 

with screw terminals. Wire sizes 4mm2 (12 

AWG) to 0.25mm2 (24 AWG).

Functions

A. 16 sequences of up to 128 steps each

B. 4 room joins with up to 3 partitions each

Ambient atmosphere requirements

Temperature: 0°C to +40°C (32°F to 104°F)

Humidity: 0 to 95% non-condensing.

Electrical and network

A. Supply: 12Vdc from the iCANnet network.

B. Counts as 1 device load when used with 4 

LED outputs or with 1 sensor.

C. Every additional 2 sensors increases the 

supply load by 1 device.

D. Will operate from 12Vdc to 18Vdc.

E. iCANnet network connection: 2 part 

connector with screw terminals. Wire sizes 

from 4mm2 (12AWG) – 0.25mm2 (24AWG).

F. Maximum wiring distance of inputs should 

not exceed 10m (32 feet).

Installation

Supplied Parts

The universal interface is supplied with a 

mounting plate for easy attachment to a 

standard double gang UK style electrical back 

box (not included).

Mounting

The mounting plate can be removed if it is 

not required, allowing the universal interface 

to be mounted in any convenient location. If 

doing so, you must ensure that the universal 

interface is supported such that it is electrically

isolated from any electrically conductive 

material in that location. The unit must be 

installed in a dry,

ventilated location where ambient temperature 

and humidity are within the operating limits of 

the product.

Содержание iLight UIG-2

Страница 1: ...UIG 2 Universal Interface Installation guide...

Страница 2: ...K style backbox and powered through the iCAN network this compact versatile unit can be mounted virtually anywhere It has four optically isolated digital inputs and a further four inputs configurable...

Страница 3: ...mA Active high voltage supply 0 25 volts E All opto isolated digital inputs wire with 2 part connectors with screw terminals Wire sizes 4mm2 12 AWG to 0 25mm2 24 AWG 4 Analogue digital inputs A Indivi...

Страница 4: ...vice load when used with 4 LED outputs or with 1 sensor C Every additional 2 sensors increases the supply load by 1 device D Will operate from 12Vdc to 18Vdc E iCANnet network connection 2 part connec...

Страница 5: ...CAN network you need to move the jumper to enable termination Operation Indicators The UIG 2 has red and green indicators visible on the front of the unit to assist with configuration and troubleshoot...

Страница 6: ...Vout supply can be used however this will bypass the optical isolation To use this supply connect 12Vout to 12Vin and 0V to 0Vopto at the connector Switch closure is made between the input and 0Vopto...

Страница 7: ...amming of simple room join functions by using partitions The room join function operates by linking areas A physical room partition can be detected by a switch on the UIG 2 inputs When the partition i...

Страница 8: ...mproper service There are no warranties which extend beyond the hereinabove limited warranty INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WARRANTY OF FITNESS No...

Отзывы: