Eaton - Lighting Systems iLight Product Series - UIG-2 73-898-00 IM8840 Iss.02 5
iCAN Network Connections
Connection to the iCAN network is made via a
removable 5-way connector block.
Network Termination
The iCAN network follows a daisy chain
topology that requires termination on the
devices located at either end of the network.
The UIG-2 is supplied with termination
disabled as standard. If it is connected as an
end device in the iCAN network, you need to
move the jumper to enable termination.
Operation Indicators
The UIG-2 has red and green indicators,
visible on the front of the unit, to assist
with configuration and troubleshooting.
iCANnet Identification Button
The UIG-2 features a small button, accessible
through the front panel, which sends an
identification message across the iCANnet
network when pressed.
Function
Network Cable Colours
0V
Black
CAN L
White
Shield
Silver
CAN H
Blue
+12Vdc
Red
IMPORTANT NOTE: Connecting a mains potential
cable to the iCAN Network terminals is likley to
damage the unit and other devices connected, and
invalidate warranty.