Manual Operations

 

  Move the slide knob to MANUAL position to expose the manual operating shaft. The control power 

supply is cut off automatically. 

  Insert the operating key into shaft slot. Turn the key clockwise to verify the breaker can be closed 

and opened. 

  Leave breaker in the ON position.

 

Press the manual PUSH-TO-TRIP button on the breaker to verify 

that the breaker moves to the trip position. 

  Turn the operating key clockwise (approximately 180

°

) again. This should reset the breaker. 

  Status window indicates Green / OFF, Red / ON and White / Tripped. 

  Always remove the operating key and move the slide knob to the AUTO position before operating 

electrically. 

 

Slider knob   

PUSH-TO-TRIP Button

Turn the key 
(Clockwise Only)   

Operating key 

Status Indication 
Window 

Содержание IL01222025E

Страница 1: ...EQUIPMENT WHILE IT IS ENERGIZED DEATH OR SEVERE PERSONAL INJURY CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING 1 CONTENTS Motor operator 1x Mounting Screws 103 5 mm 4x Mounting Screws 103 5mm Groove 4x Mounting Screws 10 mm 4x Springwashers φ4mm 8x Washers φ4mm 8x Nut M4 4x WARNING ...

Страница 2: ...ition first Line up breaker handle and molded trigger of motor operator and position motor operator on the breaker 4 Molded Trigger Mounting Screws 10 mm Lock washers Flat washers Breaker Handle Mount motor operator to breaker using mounting screws lock washers and flat washers supplied Torque to 0 44 to 0 6 N m or 4 to 5 in lb Mounting Screws 10 mm Spring washers Flat Washers Mounting Screws 103 ...

Страница 3: ...ed Leave breaker in the ON position Press the manual PUSH TO TRIP button on the breaker to verify that the breaker moves to the trip position Turn the operating key clockwise approximately 180 again This should reset the breaker Status window indicates Green OFF Red ON and White Tripped Always remove the operating key and move the slide knob to the AUTO position before operating electrically Slide...

Страница 4: ...rush Current 208 240 VAC 110 127 VAC 50 60 Hz 220 250 VDC 110 125 VDC DC 1 A 24 VDC DC 3 A 48 VDC DC 2 A 1 A minimum 150 VA power source is recommended 2 Maximum rate of operation 6 operations per minute 208 240VAC 220 250VDC Application 24VDC Application 110 127VAC 110 125VDC Application 24VDC 48VDC Application ...

Страница 5: ... is located in the AUTO position Operating the OFF remote control switch will cause the breaker to go to its OFF position Operating the ON remote control switch will cause the breaker to go to its ON position Press the manual PUSH TO TRIP button on the breaker to verify that the breaker moves to the trip position Operating the OFF remote control switch again will reset the breaker Status window in...

Страница 6: ...Page 6 IL01222025E Pittsburgh PA U S A Effective 11 2007 IL01222025E 9 Motor Operator Outline Dimensions ...

Отзывы: