Page 2
IL01222025E
Effective 11/2007
2
Assemble four mounting screws with nuts and washers.
Torque to 0.44 to 0.6 N.m or 4 to 5 in lbs. Note: Mounting
screws with groove are for use with PAD 13D Plug – in.
3
•
Turn breaker to the “OFF” position first.
•
Line up breaker handle and molded trigger of
motor operator, and position motor operator on
the breaker.
4
Molded Trigger
Mounting Screws(10 mm)
Lock washers, Flat
washers
Breaker Handle
Mount motor operator to breaker
using mounting screws, lock
washers and flat washers
supplied. Torque to 0.44 to 0.6 N.m
or 4 to 5 in. lb
Mounting Screws(10 mm)
Spring washers, Flat
Washers
Mounting Screws
(103.5 mm)
Washers
Springwashers
Nut