12
Eaton 93PM Integrated Battery Cabinet-Small Welded (IBC-SW) Installation Manual 164000639—Rev 03
•
Maximum Relative Humidity: 5–95%, noncondensing
CAUTION
It is recommended for optimal battery life and discharge performance to keep the ambient air temperature the
battery is used in at 25°C (77°F). Operating temperatures above the recommended range will result in
decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms
and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more
information. These documents can be found at
www.eaton.com/powerquality
or contact your service
representative for information on how to obtain copies.
CAUTION
The shelf life for the batteries installed in the IBC is 12 months from the date code on the battery. The recharge
date is also stated on a label inside the IBC.
Failure to recharge the batteries before the expiration of the shelf life will result in reduced discharge time,
shorter float service life, and will void the warranty.
The IBC–SW operating environment must meet the weight requirements shown in
and the size
requirements shown in
through
. Dimensions are in millimeters (inches). Specifications are
subject to change.
Table 1. IBC-SW Cabinet Weights
Model
Weight kg (lb)
Voltage
Shipping
Installed
Point Loading
Eaton 93PM IBC–SW
with 1 battery string (36 batteries)
432V
935 (2061)
908 (2001)
6 at 151 (334)
Eaton 93PM IBC–SW
with 1 battery string (40 batteries)
480V
1007 (2219)
980 (2159)
6 at 163 (360)
Eaton 93PM IBC–SW
Shipped without batteries
432V
301 (665)
Eaton 93PM IBC–SW
Shipped without batteries
480V
303 (667)
The IBC–SW uses natural convection cooling to regulate internal component temperature. Air inlets are in the
front of the cabinet and outlets are on the back or top of the cabinet. Allow clearance in front of, and on back or
top of the cabinet for proper air circulation. The clearances required around the IBC–SW cabinet are shown in
.