Sensitivity Adjustments
Ultrasonic Sensitivity

 (Green LED) – Using a small flathead screw driver turn the 

green potentiometer so that the arrow points UP.

1.  Stand in different areas of the room and wave your hands.
2.  If the Green LED does not turn ON, increase the US sensitivity by turning the 

green potentiometer clockwise in small increments. Repeat Step 1.

3.  Stand still three to four feet away from sensor for five seconds. LED should 

not turn ON

.

4.  If Green LED turns ON without motion or is constantly ON, decrease the 

US sensitivity by turning green potentiometer counter-clockwise in small 
decrements. Repeat Step 3.

Note:

 

Do Not adjust sensitivity higher than necessary.

PIR Sensitivity

1.  Stand in different areas of the room and wave your hands.
2.  If the Red LED does not turn ON, check for any obstructions.
3.  Stand still three to four feet away from sensor for five seconds. LED should not turn ON

.

4.  If Red LED turns ON without motion or is constantly ON adjust PIR sensitivity to 50 % by moving DIP Switch 5 up.

Field-of-view outside the space

1.  Adjust PIR sensitivity to 50% by moving DIP Switch 5 up.
2.  Use non-reflective tape strips to cover the portions of the sensor lens that view outside the space.
3.  Adjust Ultrasonic Sensitivity.

ON/OFF Disabled Feature

1.  ON/OFF Button Disable Option – When selected this 

option disables the ON/OFF button and sensor becomes 
automatic only control regardless of the setting for 
automatic or manual activation. This feature will not 
allow someone to turn light(s) OFF via the pushbutton 
while people are in common areas such as restroom, 
break room, and copy room areas.

Daylight Adjustments

The Daylighting feature prevents the lights from turning ON when the room is adequately illuminated by natural light. If there is 

enough light in the room regardless of occupancy, the sensor will hold the lights OFF. If there is not enough light in the room, the 
sensor will allow the lights to turn ON when occupied. The sensor will not allow the Daylighting feature to turn the load OFF until the 
space is vacant or the light level rises above the setpoint and the time delay expires. While in Manual Activation Mode, if someone 
attempts to turn the load ON and there is sufficient daylight available the Daylighting feature will hold the lights OFF.

1.  Set the light level when the ambient light is at the level where no artificial light is needed. If this feature is not needed, leave the 

light level at maximum (fully CW).

2.  With the load(s) ON, put the sensor into Test Mode. To place into Test Mode, toggle DIP Switch 8 out of its current position, wait 

3 seconds and then back in to its original position.

3.  Set the Light level to minimum (fully CCW).
4.  Let the sensor Time-out so lights are OFF. Enter the space and lights should remain OFF.
5.  Make sure not to block the sensor from the daylight source and adjust the light level potentiometer CW in small increments. 

(Pause 5 seconds between each adjustment)

6.  Lights will not turn ON upon occupancy activation, when the ambient light level exceeds the daylight threshold setting.

Time Delay Adjustments

People who remain very still for long periods of time 

may need a longer time delay than the default setting of 10 
minutes. As long as the self-adjusting feature is enabled, the 
switch will respond to each pair of false-OFFs with no normal 
OFF in between, by alternately making slight adjustments to 
either time delay (by 2 minute increments) or sensitivity, so 
there should be no need for manual adjustment. If manual 
adjustment is desired, refer to Time Delay settings in DIP 
Switch legend.

Reset sensor time delay to factory settings by moving DIP 

Switches 1 and 2 down. (If DIP Switches 1 and 2 are already down, toggle DIP Switch 1 out of its current position, wait 3 seconds, 
and then back to its original position)

Override

The Override setting allows the sensor to operate as a service switch in the unlikely event of failure.
1.  Move DIP Switch 12 up.
2.  The pushbutton can be used to manually turn lights ON or OFF.

Warranties and Limitation of Liability  

DIP Switch Settings  

Troubleshooting

Please refer to www.coopercontrol.com under the Legal section for our terms and conditions.

Checkout and Adjustment  

LOAD 1

BLACK

BLUE

NEUTRAL

THREE-WAY WIRING DIAGRAM:
LIGHTS WILL TURN OFF, WHEN UNIT THAT WAS TURNED ON LAST AND/OR DETECTED MOTION LAST TIMES-OUT.

GROUND

GREEN

120/277 VAC

BLACK

BLUE

GROUND

GREEN

TRAVELLER 

WIRES

Wiring Diagram 3: 

120/277 VAC single level single circuit three-way wiring diagram

CAUTION: If a room is wired for two circuits using two separate hot leads, it is very important to connect only one circuit 

per relay. Both circuits must be fed from the same phase.

Issue

Possible Causes

Suggestions

Lights  

Will Not 

Turn ON  

automatically

Sensor is in Manual ON mode

Press pushbutton. If Auto Mode 

is desired change Activation Mode to Auto.

Sensor was turned OFF manually. If the  

Sensor was turned OFF manually before  

the time delay expired, lights will remain  

OFF for the remainder of the time delay.

Press the pushbutton to turn the lights back ON

.

Daylighting Feature Enabled

If all lights are required to turn ON  

adjust daylight potentiometer.

Power interruption

Check incoming voltage and/or wiring

Lights  

Will Not  

Turn ON  

manually

Daylighting Feature Enabled

If all lights are required to turn ON  

adjust daylight potentiometer.

Power interruption

Check incoming voltage and/or wiring

ON/OFF Button Disabled

Move DIP Switch 7 down

If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879

Lights  

Will Not  

Turn OFF  

automatically

Override

Make sure sensor is not in Override Mode. (DIP Switch 8 up)

Self-Adjust

If sensor is in Self-Adjust Mode, it may be possible for the 

unit to have increased the time delay to a 30 minute delay. 

If the lights do not turn OFF after 30 minutes follow next step.

30 Minute Delay

Maximum time delay is 30 Minutes. Check DIP  

Switches to verify DIP Switch settings. If lights do  

not turn OFF at the set Time Delay, check next step.

Ultrasonic Sensitivity set High

Lower sensitivity by turning green  

potentiometer CCW in small decrements.

PIR activated by heat source other than occupant

Move DIP Switch 5 up.

Lights  

Will Not  

Turn OFF  

manually

Call Technical Services

ON/OFF Button Disabled

Move DIP Switch 7 down

If lights will still not turn OFF, call Technical Services at 1-800-553-3879

1 2 3 4 5 6 7 8

5 Minutes

15 Sec Test/Auto*

Time Delay

DIP Switch

Activation

PIR Sensitivity

Not Used

Override

Maintain Lights On

Not Used

Relay 1

Not Used

ON/OFF Button

Walk-Through Mode

15 Minutes

1

2

DIP Switch Legend

12

11

9

6


Disable
Enable

4

3


Auto
Manual

5


Full
50%

8



Enable
Disable

7

Disable
Enable

10


Either
Both

Default = 

30 Minutes

*Self-Adjusts to

10 min. user 

mode

9 10 11 12

Adjustments should be made with the HVAC system ON so that the installer will be able to detect the effect of airflow on the 

operation of the ONW-D-1001-MV. Use only insulated tools to make adjustments.

Immediately after applying power to the lighting circuit, wait approximately two minutes for the switch to power-up and stabilize.

Self-Adjust

Sensor is shipped in self-adjust mode. This applies to time 

delay, US and PIR sensitivity. In preparation for the Installer 
Test, the time delay is set to 15 seconds, after the sensor is 
installed, powered ON and has stabilized, the unit will time-
out 15 seconds after the last motion detected. Coverage and 
sensitivity can be confirmed by watching the Green (US) and 
Red (PIR) indicator LEDs on the front of the sensor, while 
moving around the room.

1.  Walk around the room and monitor LEDs.
2.  Stand in different parts of the room and wave your 

hands. LEDs should only turn ON for one second with 
each motion. (If LEDs do not turn ON, go to Installer 
Adjustments – Sensitivity Adjustment Section)

3.  Stand still three to four feet away from sensor for five 

seconds. LEDs should not turn ON. (If any LED turns ON, 
note LED and go to Installer Adjustments – Sensitivity 
Adjustments section)

4.  Walk outside the room and wait 15 seconds for the lights to turn OFF. (If lights do not turn OFF go to Installer  

Adjustments Section)

5.  Re-enter the room to activate sensor. (If lights do not turn ON go to Troubleshooting Section)
6.  At this point you can exit the room and let the sensor time-out. When the sensor times-out and is OFF with power ON for five 

minutes, the unit will go to a 10 minute Time Delay user mode setting.

Note:

 

To place into Test Mode, toggle DIP Switch 12 out of its current position, wait 3 seconds, and then back into its original position.

ON/OFF Button

PIR Lens

DIP Switches

Ultrasonic Detection

Daylight 

Sensor Level 

Adjustment

Ultrasonic 

Sensitivity 

Adjustment

Red (PIR) & Green (US) 

Detection LEDs

1 and 2

1

2

3 4

5 6 7 8

9 10 11 12

1 2 3 4 5 6

7 8 9 10 11 12