Eaton Ferrups FX UPS P-164000906 Eaton Ferrups FX User’s Guide P-164000906—Rev 05
37
Changing a Parameter
To display a parameter, press [DISPLAY], the parameter number, and [ENTER]. To change a parameter press
[PROGRAM] enter the value then press [ENTER] follow these steps:
Table 18. Changing a Parameter
Press This Key
Display Shows
[DISPLAY] [0] [ENTER]
00 Time 07:04:08
[PROGRAM]
00 Pgm:
[9] [3] [0]
00 Pgm: 930
[ENTER]
00 Time 09:30:00
77..55
U
UP
PS
S P
Paarraam
meetteerrss
NOTE
Only qualified technicians using the proper metering equipment should change other
parameters. Improper calibration may cause the Eaton FX FERRUPS UPS to
malfunction. Call your
service representative before you attempt to change any
parameters except any parameter mentioned in the Initial parameter setup.
Table 19. Parameter List
Parameter
Number
Sample / Default
Password Level
Range
Description
.
"Temp Ambient 38 C"
No Change
Allowed
Ambient, InvTop,
InvBot, Xfmr,
Charger, AcScr,
Dvr1, Dvr2
Display cycles through all temperatures.
Scrolls to next temperature every 3 seconds.
User can toggle scrolling by pressing '0'.
When scrolling is stopped, pressing '1' will
move to next temperature. List will wrap.
0
“00 Time 12:00:00”
User
00:00:00
-23:59:59
Time of day using 24-hr military time. Time
is set to last known time whenever UPS is
turned on.
1
“01 V In 120.0 V”
Service
0.0 – 500.0
Measured RMS voltage of the UPS line
input cord.
2
“02 V Out 120.0 V”
Service
0.0 – 500.0
Measured RMS voltage of the UPS outlets
to the load. Programming changes an
internal setting to calibrate reading.
3
“03 I In 10.0 A”
Service
0.0 – 220.0
Measured RMS current of the UPS line
input cord. Programming changes an
internal setting to calibrate reading.
4
“04 I Out 3.1 A”
Service
0.0 – 220.0
Measured RMS current of the UPS outlets
to the load. Programming changes an
internal setting to calibrate reading.
6
“06 I Batt 0.0 A”
Service
0.0 – 200.0
When the unit is on battery, this is the
discharge current. Otherwise, this is the
charging current. Programming changes an
internal setting to calibrate reading.
Содержание Ferrups FX
Страница 1: ...p n P 164000906 Revision 05 Ferrups FX UPS Eaton Ferrups FX User s Guide Eaton Ferrups FX UPS...
Страница 8: ...viii Eaton Ferrups FX UPS P 164000906 Eaton Ferrups FX User s Guide P 164000906 Rev 05 List of Figures...
Страница 18: ...8 Eaton Ferrups FX UPS P 164000906 Eaton Ferrups FX User s Guide P 164000906 Rev 05 Communication Overview...
Страница 82: ...72 Eaton Ferrups FX UPS P 164000906 Eaton Ferrups FX User s Guide P 164000906 Rev 05 Service and Support...
Страница 88: ...78 Eaton Ferrups FX UPS P 164000906 Eaton Ferrups FX User s Guide P 164000906 Rev 05 Battery...
Страница 90: ...P 16400090605 P 164000906 05...