![Eaton FDF120 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/eaton/fdf120/fdf120_technical-data-manual_4064533008.webp)
Technical Data and Specifications - LMR Plus Electric Controllers
Technical Data and Specifications - DIESEL Plus Diesel Engine Controllers
Line Terminals on Main Isolation Switch (Incoming Cables)
Load Terminals (To Motor)
Line Terminals (Incoming Cables)
Recommended Wire Size
I/O Board
Battery Wire
Stranded # 14 (1.63 mm)
Stranded # 10 (2.59 mm)
Stranded # 14 (1.63 mm)
Stranded # 8 (3.26 mm)
Engine Board
Stranded # 14 (1.63 mm)
Terminal Number
11, 34-49, 60-95
6, 8, 11
Option Board Terminals
6, 8, 11
1-5, 9, 10, 12, 301, 302, 303, 304, 310, 311, 312, L, N, G
Distance
N. A.
N. A.
N. A.
0 feet to 25 feet (7.62m)
25 feet to 50 feet (7.62 - 15.24m)
Qty. & Cable Sizes
American Wire Gauge (AWG /MCM)
Diameter (mm)
(1)#4-#3 PER Ø (CU)
(1)#4-4/0 PER Ø (CU/AL)
(1)#6-250MCM PER Ø (CU/AL)
(2)1/0-250MCM PER Ø (CU/AL)
(2)2/0-500MCM PER Ø (CU/AL)
For Proper Cable Size Refer to National Electrical Code NFPA-70.
(1.63 - 5.83 mm)
(1.63 - 8.25 mm)
(4.11 -12.70 mm)
((8.25 - 12.70 mm)
((9.27 - 17.96 mm)
Qty. & Cable Sizes
American Wire Gauge (AWG /MCM)
Diameter (mm)
(1)#14-1/0 PER Ø (CU/AL)
(1)#4-4/0 PER Ø (CU)
(1)#3-350MCM PER Ø (CU/AL)
(2)3/0-250MCM PER Ø (CU/AL)
(2)2/0-250-350MCM PER Ø (CU/AL)
(2)#1-500MCM PER Ø (CU/AL)
(3)3/0-400MCM PER Ø (CU/AL)
(1.63 - 5.83 mm)
(5.83 - 11.68 mm)
(5.83 -15.03 mm)
((10.40 - 12.70 mm)
((7.35 - 17.96 mm)
((12.70 - 15.03 mm)
((10.40 - 16.06 mm)
Service Entrance Ground Lug - Qty. & Cable Sizes
American Wire Gauge (AWG /MCM)
Diameter (mm)
(1)#14-2/0 PER Ø (CU/AL)
(1)#4-350MCM PER Ø (CU/AL)
(2)1/0-750MCM PER Ø (CU/AL)
(1.63 - 9.27 mm)
(5.19 - 15.03 mm)
(8.25 -22.00 mm)
Technical Data TD081023EN
Wire & Cable Conversions
Effective April 2015
LMR Plus Fire Pump Controllers
Diesel Plus Engine Controllers
N. Y. C.
APPROVED
U.B.C and C.B.C
Must Be Installed Per Applicable Code
and Manufacturers Recommendations
SEISMIC QUALIFIED