EZD operation
For more information visit:
www.EatonElectrical.com
MN05013005E
19
Status display for local expansion
EZD advanced Status display
EZD LED display
EZD features two LEDs on the back of the EZD-CP... power
supply /CPU device. These indicate the status of the power
supply (POW) and the RUN or STOP operating mode
Inputs
AC expansion ok/P buttons
Expansion
or Weekday/Date
Weekday/Time
Outputs
On: 1, 2, 3, 4/Off:…
RS = Expansion functioning correctly
R 1.........12
RS
AC P-
MO 10:42
S 1......8
STOP
Retention/debounce/
EZ-NET station
AC expansion ok/P buttons
Startup behavior
RE
: Retention switched on
I
: Debounce switched on
NT1
: EZ-NET station with station address
COM
The COM connection is active
AC
: AC expansion functioning correctly
DC
: DC expansion functioning correctly
GW
: Bus coupling module detected
GW flashes: Only EZ200-EZ detected. I/O expansion not detected.
ST
: When the power supply is switched on, EZD switches to STOP mode
I 12...6.89..12
RE
I NT1 AC P-
MO 14:42
T
Q 12345678
RUN