Page 24 - 34007724EN/AD
BY
PA
SS
NORMAL
2. Installation
Connection of battery cables
1 - Check that the battery circuit
breaker
12
is OFF ("0" position),
2 - Connect the battery power cable
28
to the connectors
6
of the power
and battery modules,
3 - Connect the battery detection cable
29
to the connectors
4
of the power
and battery modules,
Connection of galvanic isolation transformer
Output cable cross-section (not provided): 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).
z
Input cable cross-section (not provided): 10 mm², solid or stranded wire (maximum 13 mm² or AWG 6).
z
N
L
N
L
OUTPUT
INPUT
Transformer Input
Transformer Output
12
6
29
28
4