Page 26 - 34007724EN/AD
OFF
ON
UPS SET UP
EXIT ENT
OFF
ON
3. Operation
3.1 Initial start up
Check that the manual bypass switch
7
is on Normal position.
Set the normal AC source circuit-breaker
9
to the "I" position.
Set the battery circuit breaker
12
to the "I" position.
The load is powered via the bypass AC source, but not protected by
the UPS.
Batteries are recharging, an eight-hour recharge period is necessary
to get full backup time.
LED
15
is ON.
PRESS ONTO START
UPS
If specific settings are required, it is recommended to enter the UPS personnalisation mode at this stage.
It is possible to enter this mode through the front panel buttons or the
Personal Solution-Pac
software for
Windows included in the EATON
Solution-Pac
power management suite CD-ROM.
Press "scroll up"
z
19
and "scroll down"
20
function buttons
together for more than 3 seconds.
Press the function button
z
20
placed under the ENT word to
enter the set up mode and follow the LCD messages using the
buttons now defined as select keys.
Local settings
Personnalisation de la sortie
(*) : - Select "I/T Network" and "AC Bypass within tolerance" for computer loads.
- Select "Industrial" and "AC Bypass out of tolerance" in case of absolute need for service continuity
(with potential 10 ms break).
Accessing personalisation with front panel buttons
UPS personalisation
15
19
20
Function
Factory setting
Options
Language
English
French, Spanish, German, Italian.
Date / time format
International format
(DD-MM-YYYY/HH:MM)
US format (MM-DD-YYYY/HH:MM AM/PM).
Date / time change
Time in France
MM-DD-YYYY/HH:MM adjustable.
Audible alarm
Quick beeps
Slow beeps.
Function
Factory setting
Options
Comments
Output voltage
230 Volts AC
200/208/220/240/250
Frequency converter
Disabled
Enabled
Bypass AC source disabled.
Output frequency
Auto ranging
50/60 Hz
User selectable under
frequency converter mode.
Eco mode
Disabled
Enabled
See glossary.
Hot standby
Disabled
Enabled
N+1 redundancy
(See section 2.5 "Hot
standby").
Operating mode
Industrial
I/T Network
(*)
Transfer on Bypass AC
source
If the Bypass AC source
is out of tolerances
If the Bypass AC source
is inside tolerances
(*)
Break time
10 ms
10 to 200 ms
(by steps of 10 ms)
Break time calibration during
load transfer on Bypass AC
source out of tolerances.
Overload level
102 %
50/70 %
Содержание EX RT 11 3:1
Страница 2: ...3400772400 AD...
Страница 3: ...www eaton com Installation and user manual EX RT 5 3 1 EX RT 7 3 1 EX RT 11 3 1...
Страница 41: ...www eaton com Manuel d installation et d utilisation EX RT 5 3 1 EX RT 7 3 1 EX RT 11 3 1...
Страница 79: ...www eaton com Installations und Bedienungsanleitung EX RT 5 3 1 EX RT 7 3 1 EX RT 11 3 1...
Страница 117: ...www eaton com Manuale d installazione e d uso per l utente EX RT 5 3 1 EX RT 7 3 1 EX RT 11 3 1...
Страница 155: ...www eaton com Manual de instalaci n y de utilizaci n EX RT 5 3 1 EX RT 7 3 1 EX RT 11 3 1...
Страница 193: ...www eaton com Installatie en gebruiker shandleiding EX RT 5 3 1 EX RT 7 3 1 EX RT 11 3 1...
Страница 231: ...3400772400 AD...
Страница 232: ...www eaton com 3400772400 AD...