5.3 Maintenance on a UPS Equipped With the HotSwap MBP Module
The HotSwap MBP module makes possible
to service or even replace the UPS without
affecting the connected loads (HotSwap
function).
Maintenance:
1. Set switch
(53)
to the Bypass position.
The red LED
(52)
on the HotSwap MBP
module goes ON, indicating that the load
is supplied directly with AC power.
2. Stop the UPS by pressing the ON/OFF
button
(27)
on the UPS control panel. LED
(51)
“UPS ON - OK to switch” goes OFF,
the UPS can now be disconnected and
replaced.
Return to normal operation:
1. Check that the UPS is correctly connected
to the HotSwap MBP module.
2. Start the UPS by pressing the ON/OFF
button
(27)
on the UPS control panel.
LED
(51)
“UPS ON - OK to switch” on
the HotSwap MBP module goes ON
(otherwise, there is a connection error
between the HotSwap MBP module and
the UPS).
3. Set switch
(53)
to the Normal position. The
red LED
(52)
on the HotSwap MBP module
goes OFF.
86-86710-00EN A02 - Page 26
5. Troubleshooting
86-86710-00 A02 UM.indd 26
14/01/2009 10:56:30
6. Appendices
6.1 Technical Specifications
(1)
Depending on the output voltage selected: 100V / 104V / 110V /
120V
/ 127V, the output power is 1890VA /
1890VA / 2100VA /
2100VA
/ 2100VA.
(2)
Depending on the output voltage selected: 100V / 104V / 110V /
120V
/ 127V, the output power is 2500VA /
2500VA / 2500VA /
3000VA
/ 3000VA.
(3)
Standard output power is 2550 W, 2400 W with an
EXB
module.
(4)
Values for 33% / 66% / 100% of UPS output.
(5)
Programmable: 100V / 104V / 110V /
120V
/ 127V using the
UPS Config
software.
(6)
Frequency-converter mode is programmable using the
UPS Config
software.
(7)
Depending on the output voltage selected: 100V / 104V / 110V /
120V
/ 127V, the maximum output current is
18.9A / 18.2A / 19.1A /
17.5A
/ 16.5A.
(8)
Depending on the output voltage selected: 100V / 104V / 110V /
120V
/ 127V, the output current is 25A / 24A /
22.7A /
25A
/ 23.6A.
(9)
EXB is in 3U model only. Standard UPS can be connected with up to 4 EXB.
EX 2200
EX 3000
EXB
(9)
Output power
2100 VA
(1)
/
1650 W
3000 VA
(2)
/
2550 W
(3)
Electrical supply network
w
Rated input voltage
w
Input voltage range
w
Frequency
w
Power factor
w
Leakage current
100-120 V
55 / 72 / 100 to 142 V
(4)
50/60 Hz (autoselection)
> 0.95
< 2 mA
Load output
w
Voltage
w
Frequency
w
Harmonic distortion
w
Overload capacity
w
Current
100V
50/60 Hz ±0,5%
(6)
< 4% for linear load, < 6% for nonlinear load
102% continuous, 105% 20s, > 130% 1.5s
17.5 A
(7)
25 A
(8)
Battery
6 x 12V - 7 Ah,
sealed lead acid,
maintenance free
6 x 12V - 9 Ah,
sealed lead acid,
maintenance free
Two 6 x 12 V - 9 Ah
strings, sealed lead acid,
maintenance free
Environment
w
Operating temperature
range
w
Relative humidity
w
Storage temperature
range
w
Altitude
0 - 40°C (32 - 104°F )
20 - 90% (without condensation)
-20 - 40°C (-4 -104°F)
1000 m
w
Noise level
< 47 dBA
86-86710-00EN A02 - Page 27
86-86710-00 A02 UM.indd 27
14/01/2009 10:56:31
Содержание EX Pulsar Series
Страница 2: ...w P 86 86710 00...
Страница 4: ......
Страница 6: ......
Страница 9: ...3 LED LED LED CFC HCFC UPS EATON EATON UPS EATON UPS...
Страница 10: ...4...
Страница 18: ...12 86 86710...
Страница 22: ...16...
Страница 33: ...www eaton com 86 86710 00 A02 86 86710 00 A02 UM indd 34 14 01 2009 10 56 53 www eaton com...
Страница 34: ...w P 86 86710 00...
Страница 36: ......
Страница 38: ......
Страница 42: ...4 86 86710 00...
Страница 50: ...12 86 86710 00 This page left blank intentionally...
Страница 54: ...16 4 4 4 86 86710 00 This page left blank intentionally...
Страница 65: ...es 31 2009 10 56 32 2009 10 56 32...
Страница 66: ...www eaton com 86 86710 00 A02 86 86710 00 A02 UM indd 34 14 01 2009 10 56 53 www eaton com 614 03760 01...