6 Configuration
10
ESR5-VE3-42
07/20 MN049003EN
www.eaton.com
6 Configuration
▶
Disconnect the safety relay from the supply voltage.
▶
Set the delay time at the rotary switch.
▶
Restore the power supply.
WARNING
Danger due to incorrect delay time
Check the set delay time following installation!
→
If the rotary switch is modified during operation, the safety relay
switches to configuration mode and the LEDs flash.
The safety relay is only ready for operation again once the
supply voltage has been switched off and on again and configu-
ration has been carried out.